B-
12
LPS-D Line Protection System
GE Power Management
B.1 MEMORY MAPPING
APPENDIX B
B
R43386I
G1_A1
A1
0 to 256 step 1
R/W
INT
R43387I
G1_A2
A2
0 to 256 step 1
R/W
INT
R43388I
G1_A3
A3
0 to 256 step 1
R/W
INT
R43389I
G1_A4
A4
0 to 256 step 1
R/W
INT
R43390I
G1_A5
A5
0 to 256 step 1
R/W
INT
R43391I
G1_A6
A6
0 to 256 step 1
R/W
INT
R43392I
G1_A7
A7
0 to 256 step 1
R/W
INT
R43393I
G1_A8
A8
0 to 256 step 1
R/W
INT
R43394I
G1_A9
A9
0 to 256 step 1
R/W
INT
R43395I
G1_A10
A10
0 to 256 step 1
R/W
INT
R43396I
G1_A11
A11
0 to 256 step 1
R/W
INT
R43397I
G1_A12
A12
0 to 256 step 1
R/W
INT
R43398I
G1_C1
C1
0 to 256 step 1
R/W
INT
R43399I
G1_C2
C2
0 to 256 step 1
R/W
INT
R43400I
G1_KT1
KT1
0 to 256 step 1
R/W
INT
R43401I
G1_KT2
KT2
0 to 256 step 1
R/W
INT
R43402I
G1_KT3
KT3
0 to 256 step 1
R/W
INT
R43403I
G1_KT4
KT4
0 to 256 step 1
R/W
INT
R43404I
G1_CONFTRIP
CONFTRIP
0 to 256 step 1
R/W
INT
R43405I
G1_CONFOSC
CONFOSC
0 to 256 step 1
R/W
INT
R43500I
G2_Z1PHASE
Z1PHASE
0 = No; 1 = Yes
R/W
INT
R43501F
G2_Z1PHREACH
Z1PHREACH
0.01 to 50.0
Ω
step 0.01 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
R43503F
G2_Z1PLEVDET
Z1PLEVDET
0.0 to 9.9 p.u. V step 0.1
R/W
Float
R43505I
G2_Z1GROUND
Z1GROUND
0 = No; 1 = Yes
R/W
INT
R43506F
G2_Z1GRDREACH
Z1GRDREACH
0.01 to 50.0
Ω
step 0.01 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
R43508I
G2_Z1GRDCHAR
Z1GRDCHAR
0 = Mho; 1 = React
R/W
INT
R43509F
G2_Z1SUREACH
Z1SUREACH
0.01 to 50.0
Ω
step 0.01 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
R43511F
G2_Z1GROUNDK0
Z1GROUNDK0
1.0 to 7.0 step 0.1
R/W
Float
R43513F
G2_Z1GLEVDET
ZIGLEVDET
0.0 to 9.9 p.u. V step 0.1
R/W
Float
R43515I
G2_Z1BLOCK
Z1BLOCK
0 = No; 1 = Yes
R/W
INT
R43516I
G2_Z2PHASE
Z2PHASE
0 = No; 1 = Yes
R/W
INT
R43517F
G2_Z2PHREACH
Z2PHREACH
0.01 to 50.0
Ω
step 0.01 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
R43519I
G2_Z2PCHARANG
Z2PCHARANG
90 to 120° step 5
R/W
INT
R43520I
G2_Z2GROUND
Z2GROUND
0 = No; 1 = Yes
R/W
INT
R43521I
G2_Z2GRDCHAR
Z2GRDCHAR
0 = MHO; 1 = GDOC;
2 = MHOGDOC
R/W
INT
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 8 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...