![GE LPS-D Скачать руководство пользователя страница 248](http://html.mh-extra.com/html/ge/lps-d/lps-d_instruction-manual_131861248.webp)
8-
22
LPS-D Line Protection System
GE Power Management
8.2 INFORMATION
8 LOCAL USER INTERFACE
8
3.
If no digital input is assigned to a contact converter, its status information will still be displayed along with
the contact converter number but the name will be blank.
8.2.6 DIGITAL OUTPUT STATUS
This command displays the definition and the state of each digital output in the relay. This information is dis-
played three lines at a time. Use the arrow keys to scroll through the digital outputs (displayed in groups).
The Trip Outputs have the letter T in front of the output contact number. Alarm Contacts have the letter A in
front of the output contact number. The two Form C output contacts have the letter C in front of the number.
The Critical Alarm is just labeled CA.
If the DO status is shown as ‘0’ it means it is OPEN. If it is ‘1’, it is ‘CLOSED’.
8.2.7 EVENT INFORMATION
This category can be used to view event information logged when certain functions are performed by the relay.
Information displayed for each event consists of: Event number and its time of occurrence on the top line Date
of occurrence of event on the second line. Detailed event description on the third and fourth lines. The user
may use the ARROW keys to view the event information. The user can also enter an event number followed by
the [ENT] key to display the information for a specific event. An error message is displayed if the user enters
an invalid event number. Listed below is a list of the possible event messages available:
EVENT LIST
•
Fail: CPU board SRAM
•
Fail: 960 access to DPRAM
•
Fail: EEPROM
•
Fail: Digital output test
•
Fail: Interrupt test
•
Fail: ANI ADC Control logic
•
Fail: ANI ref. channel test
•
Fail: DMA interrupt failure
•
Fail: ANI board timer
•
Fail: ANI board serial EEPROM test
•
Fail: MAG module serial EEPROM test
•
Fail: Digital output serial EEPROM test
•
Fail: DTA serial EEPROM test
•
Fail: DSP PROM failure
•
Fail: DSP internal RAM
•
Fail: DSP internal RAM checksum error
•
Fail: DSP access to DPRAM
•
Fail: DSP interrupt
•
Fail: Digital input test
•
Fail: Model number - critical in nature
•
Fail: MAG module configuration mismatch
•
Fail: ANI module configuration mismatch
•
Fail: Digital input module configuration mismatch
•
Fail: Digital output module configuration mismatch
•
Fail: Trip circuit continuity monitor #1
•
Fail: Trip circuit continuity monitor #2
•
Fail: Trip circuit continuity monitor #3
•
Fail: Trip circuit continuity monitor #4
•
Fail: Trip circuit continuity monitor #5
•
Fail: Trip circuit continuity monitor #6
•
Fail: Software version error
•
Fail: DSP software version error
DO STATUS
T1 - T4 : 1 0 1 1
T5 - T6 : 0 0
A1 - A4 : 0 1 0 0
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...