![GE LPS-D Скачать руководство пользователя страница 136](http://html.mh-extra.com/html/ge/lps-d/lps-d_instruction-manual_131861136.webp)
2-
70
LPS-D Line Protection System
GE Power Management
2.5 REFERENCE TABLES
2 CALCULATION OF SETTINGS
2
2.5.3 GENERAL SETTINGS GUIDE
Table 2–9: GENERAL SETTINGS GUIDE (Sheet 1 of 3)
No.
M nem onic
Description
Range (5A & 1A)
Step
Default
CONFIGURE
101
U N IT ID
Unit ID
0000 to 9999
1
0000
102
SYSFREQ
System Frequency
50 Hz, 60 Hz
N/A
60Hz
103
PHASROTATE
Phase Rotation
ABC, ACB
N/A
ABC
104
TIMESYNCH
Time Synch Source
INTERNAL, IRIG-B
N/A
INTERNAL
105
NUM_BKR
Number of Breakers
1, 2
N/A
1
106
NUM_TC
Number of Trip Circuits
1, 2
N/A
1
107
NUM_MON
Number of Trip Circuit
Monitors
(T6
→
T1)
format = abcdef
a-f = 0 (on) or 1 (off)
000000 (0)
T1 to T6 off
108
DISPLAYVAL
Value Display Mode
PRI, SEC
N/A
SEC
109
LANGUAGE
Language Option
ENGLISH,
SPANISH
N/A
ENGLISH
110
SYSIN1-4
System Inputs 1 to 4
0000 to 1111 (bin)
0 to 15 (dec)
1
0000
COMMPORTS
201
C O M P O R T1
Communications Port #1
Settings
Baud Rate (xx),
Parity (y),
Stop Bits (z)
format = xxyz
xx = 03, 12, 24, 48,
96, 19;
y = 1 (none), 1
(odd), 2 (even)
z = 1, 2
9601
202
COMPORT2
Communications Port #2
Settings
Interface (i), Baud
Rate (xx), Parity (y),
Stop Bits (z)
format = ixxyz
i = 0 (RS232), 1
(RS485), xx = 03,
12, 24, 48, 96, 19; y
= 0 (none), 1 (odd),
2 (even); z = 1, 2
09601
203
COMPORT3
Communications Port #3
Settings
Interface (i), Baud
Rate (xx), Parity (y),
Stop bits (z)
format = ixxyz
i = 0 (RS232), 1
(RS485), xx = 03,
12, 24, 48, 96, 19; y
= 0 (none), 1 (odd),
2 (even); z = 1, 2
09601
204
PROTOCOL1
Communications Port #1
Protocol
GE-MODEM,
ASCII, DNP 3.0
N/A
GE-MODEM
205
PROTOCOL2
Communications Port #2
Protocol
GE-MODEM,
ASCII, DNP 3.0
N/A
GE-MODEM
206
PROTOCOL3
Communications Port #3
Protocol
GE-MODEM,
ASCII, DNP 3.0
N/A
GE-MODEM
†
Setting/value is applicable to LPS-D Three Phase Tripping models only.
‡
Setting/value is applicable to LPS-D Single Phase Tripping models only.
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...