![GE LPS-D Скачать руководство пользователя страница 134](http://html.mh-extra.com/html/ge/lps-d/lps-d_instruction-manual_131861134.webp)
2-
68
LPS-D Line Protection System
GE Power Management
2.5 REFERENCE TABLES
2 CALCULATION OF SETTINGS
2
1831
S Y N C M A N C LS
Supervise Manual Close
YES, NO
NO
1832
VBUSLIVE
Live Bus Voltage
0.1 to 130 volts step 0.1
50 V
1833
VBUSDEAD
Dead Bus Voltage
0.1 to 130 volts step 0.1
50 V
1834
VLINELIVE
Live Line Voltage
0.1 to 130 volts step 0.1
50 V
1835
VLINEDEAD
Dead Line Voltage
0.1 to 130 volts step 0.1
50 V
1836
LBUSDLINE
Live Bus Dead Line
YES, NO
NO
1837
DBUSLLINE
Dead Bus Live Line
YES, NO
NO
1838
DBUSDLINE
Dead Bus Dead Line
YES, NO
NO
1839
DELTAV
Voltage Difference
0.1 to 130 volts step 0.1
10 V
1840
DELTAVBLK
Block Synch Check by DELTAV
YES, NO
NO
NONCRIT_AL (IN ADDITION TO SELF-TEST ALARMS)
1901
N C A IN 1
Non-Critical Alarm Input #1
These 8 inputs are ORed
together and then outputted to
the contact assigned to the
Non-Critical Alarm
0 to 256 step 1
48
1902
NCAIN2
Non-Critical Alarm Input #2
0 to 256 step 1
49
1903
NCAIN3
Non-Critical Alarm Input #3
0 to 256 step 1
50
1904
NCAIN4
Non-Critical Alarm Input #4
0 to 256 step 1
51
1905
NCAIN5
Non-Critical Alarm Input #5
0 to 256 step 1
0
1906
NCAIN6
Non-Critical Alarm Input #6
0 to 256 step 1
0
1907
NCAIN7
Non-Critical Alarm Input #7
0 to 256 step 1
0
1908
NCAIN8
Non-Critical Alarm Input #8
0 to 256 step 1
0
OUTPUTS
2001
T 1
T1 Contract
0 to 256 step 1
33
2002
T2
T2 Contact
0 to 256 step 1
34
‡
; 33
^
2003
T3
T3 Contact
0 to 256 step 1
35
‡
; 33
^
2004
T4
T4 Contact
0 to 256 step 1
33
‡
2005
T5
T5 Contact
0 to 256 step 1
34
‡
2006
T6
T6 Contact
0 to 256 step 1
35
‡
2007
A1
A1 Contact (configurable)
0 to 256 step 1
33
‡
; 58
^
Table 2–8: PROTECTION SETTINGS GUIDE (Sheet 8 of 9)
No.
M nem onic
Description
Range (5A)
Range (1A)
Default
†
Setting/value is applicable to LPS-D Revision B models only.
‡
Setting/value is applicable LPS-D Single Phase Tripping models only.
^
Setting/value is applicable to LPS-D Three Phase Tripping models only.
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...