B-
16
LPS-D Line Protection System
GE Power Management
B.1 MEMORY MAPPING
APPENDIX B
B
R43659I
G2_POSSEQANG
POSSEQANG
25 to 90° step 1
R/W
INT
R43660I
G2_ZERSEQANG
ZERSEQANG
25 to 90° step 1
R/W
INT
R43661F
G2_ZLINE
ZLINE
0.01 to 50 W step 0.01
0.05 to 250 W step 0.05
R/W
Float
R43663F
G2_ZEROSEQK0
G2_ZEROSEQK0
1.0 to 7.0 step 0.1
R/W
Float
R43665F
G2_LINELENGTH
LINELENGTH
0.0 to 500.0 step 0.1
R/W
Float
R43667I
G2_LINEUNIT
LINEUNIT
0 = Miles, 1 = Km
R/W
INT
R43668I
G2_CTRATIO
CTRATIO
1 to 5000 step 1
R/W
INT
R43669I
G2_PTRATIO
PTRATIO
1 to 7000 step 1
R/W
INT
R43670F
G2_FLTLOCK
FLTLOCK
0 to 99.9 sec. step 0.1
R/W
Float
R43672I
G2_FLTRESET
FLTRESET
0 to 999 minutes step 1
R/W
INT
R43673I
G2_MOBZONE
MOBZONE
0 = Zone 2; 1 = Zone 3;
2 = Zone 4
R/W
INT
R43674I
G2_MOBCHARANG
MOBCHARANG
30 to 130° step 1
R/W
INT
R43675I
G2_BLOCKWHAT
BLOCKWHAT
0 = BLKALL; 1 = BLKDIST;
2 = BLKPHAS; 3 = BLKNONE
R/W
INT
R43676I
G2_BLOCKZ1
BLOCKZ1
0 = No; 1 = Yes
R/W
INT
R43677I
G2_BLOCKZ2
BLOCKZ2
0 = No; 1 = Yes
R/W
INT
R43678I
G2_BLOCKZ3
BLOCKZ3
0 = No; 1 = Yes
R/W
INT
R43679I
G2_BLOCKZ4
BLOCKZ4
0 = No; 1 = Yes
R/W
INT
R43680I
G2_USE_OST
USE_OST
0 = No; 1 = Yes
R/W
INT
R43681I
G2_NUMBRCHAR
NUMBRCHAR
2, 3
R/W
INT
R43682I
G2_TRIPIN_OUT
TRIPIN_OUT
0 = IN; 1 = OUT
R/W
INT
R43683F
G2_FWDREACH
FWDREACH
0.1 to 75.0
Ω
step 0.1 (5A)
0.5 to 375.0
Ω
step 0.5 (1A)
R/W
Float
R43685F
G2_REVREACH
REVREACH
0.1 to 75.0
Ω
step 0.1 (5A)
0.5 to 375.0
Ω
step 0.5 (1A)
R/W
Float
R43687I
G2_OUTER
OUTER
40 to 165° step 1
R/W
INT
R43688I
G2_MIDDLE
MIDDLE
40 to 165° step 1
R/W
INT
R43689I
G2_INNER
INNER
40 to 165° step 1
R/W
INT
R43690I
G2_TLOS1PU
TLOS1PU
1 to 100 msec. step 1
R/W
INT
R43691I
G2_TLOS1DO
TLOS1DO
1 to 100 msec. step 1
R/W
INT
R43692I
G2_TLOS2PU
TLOS2PU
1 to 100 msec. step 1
R/W
INT
R43693I
G2_TLOS3PU
TLOS3PU
1 to 100 msec. step 1
R/W
INT
R43694I
G2_TLOS4PU
TLOS4PU
1 to 100 msec. step 1
R/W
INT
R43695I
G2_RECLMODE
RECLMODE
0 = Off; 1 = None; 2 = Internal;
3 = External; 4 = Both
R/W
INT
R43696I
G2_RECLOSETYPE
RECLOSETYPE
0 = 1POLE; 1 = 3 POLE;
2 = 1POLE3POLE
R/W
INT
R43697I
G2_NUM_1P_AT
NUM_1P_AT
1, 2, 3, 4
R/W
INT
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 12 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...