background image

(datum / name): 10.12.08 Su/Fz 

Z. Nr.: 1004 0710.2

Page  1  von  4 

Type: MSF 220 SE

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected] 

Operating manual 

MSF 220 SE 

Application 

The PTC-resistor trip device MSF 220 SE monitors the winding temperature of machines and 
equipment.  Signals,  that  can  be  used  as  ”early  warning"  or  ”malfunction"  (switching-off),  are 
transmitted as soon as the admissible limit temperature is exceeded. 
Two  PTC-circuits  can  be  connected  to  this  unit.  The  integrated  rise-delay  time  ensures  a 
reliable mains voltage build-up. 

Function 

*

2 PTC resistor circuits, 1 to 6 PTC each (max. cold resistance of circuit 1500

 each)

*

potential-free contact for alarm 1

*

potential-free contact for alarm 2

*

voltage of pin 3 is connectet to pin 1 with a time delay of 2 sec., replacing  an additional
timing relay.

*

alarm 3 for check of relay K3

*

LED´s signal state of relays K1 and K2

*

relay K3 picks up time-delayed

Note 

Thanks to the delayed switching-on of the  error message (approx. 2 s) after the switching-on, 
this device is especially suitable where an auxiliary voltage is not available and the secondary 
voltage of the monitored transformer is being used. The MSF-200 SE can furthermore be used 
advantageously when combining it with operating current releases. For additional devices, the 
control  voltage  is  available  at  terminal  1  time-delayed.  In  case  of  a  breakdown  of  the  supply 
voltage,  the  control  voltage  is  available  at  terminal  7  and  can  be  used  as  a  message. 
(Attention! This message will also be given  for approx. 2 s. after switching-on.) 

Functional description 

PTC-circuits  in  closed-circuit  current  principle.  When  the  closed-circuit  current  flows,  both 
output relays K1, K2 are picked up. Approx. 2 sec. after switching  on supply power, relay K3 
picks up time-delayed, closing the contact circuits at terminals 31, 14 and 31, 24. As soon as 
the  temperature  of  the  early  warning  has  been  reached,  relay  K1    releases  (terminal  31,  12 
closed),  the  alarm  1  is  given.  If  the  temperature  of  malfunction  is  reached,  also  relay  K2 
releases (terminal 31, 22 closed). This alarm 2 can be used to switch off the equipment. If the 
temperature drops to approx. 5 °C below the temperature of malfunction or early warning, the 
relays K1 and K2 resp. are switched on again. 

MINIPAN

®

 digital panel meters, temperature- and mains controlling,

special purpose instruments for customer requirements    

www.ziehl.com

 

- Archive document

www.ziehl.de

Содержание MSF 220 SE

Страница 1: ... not available and the secondary voltage of the monitored transformer is being used The MSF 200 SE can furthermore be used advantageously when combining it with operating current releases For additional devices the control voltage is available at terminal 1 time delayed In case of a breakdown of the supply voltage the control voltage is available at terminal 7 and can be used as a message Attentio...

Страница 2: ...current max 8 A Switching power max 2000 VA Rated continious current Ith 5 A Rated operational current Ie 2 A AC15 400 V 2A DC13 24 V 3 A AC15 250 V Prefuse for device and contacts AC T 4 A DC T 2 A Mechanical contact life 3 x 107 operations Electrical contact life 1 x 105 operations at max switching capacity Factor of reduction at cos 0 4 0 5 x max switching capacity Switching on delay app 2 s Te...

Страница 3: ...rminals A1 and A2 When device is ready for operation relays K1 and K2 switch on immediately the LED s are off After approx 2 s relay K3 picks up terminals 31 14 31 24 31 34 are connected Relay K1 releases as soon as the input at terminal T11 T12 becomes high resistive Relay K2 releases as soon as the input at terminal T21 T22 becomes high resistive Relay K1 K2 pick up as soon as the inputs at term...

Страница 4: ... 12 K1 34 32 K3 2 circuit 2 K2 6 3 circuit 1 PTC s alarm 1 alarm 2 operation 2 delayed input signal of terminal 3 alarm 3 A2 A1 Us DC AC T11 T21 T12 T22 input signal operation 1 104 5 82 36 23 5 5 41 5 80 34 1 2 3 4 5 6 7 8 9 10 11 12 82 41 5 17 7 5 5 11 5 17 5 5 10 1 2 3 1 1 2 6 Jackets for co ding pins 14 27 5 2 3 1 Cable bushing Mounting bore hole Unlatching only with rail mounting Base 41 16 3...

Отзывы: