APPENDIX B
B.1 MEMORY MAPPING
B
R44270F
G4_FLTLOCK
FLTLOCK
0 to 99.9 sec. step 0.1
R/W
Float
R44272I
G4_FLTRESET
FLTRESET
0 to 999 minutes step 1
R/W
INT
R44273I
G4_MOBZONE
MOBZONE
0 = Zone 2; 1 = Zone 3;
2 = Zone 4
R/W
INT
R44274I
G4_MOBCHARANG
MOBCHARANG
30 to 130° step 1
R/W
INT
R44275I
G4_BLOCKWHAT
BLOCKWHAT
0 = BLKALL; 1 = BLKDIST;
2 = BLKPHAS; 3 = BLKNONE
R/W
INT
R44276I
G4_BLOCKZ1
BLOCKZ1
0 = No; 1 = Yes
R/W
INT
R44277I
G4_BLOCKZ2
BLOCKZ2
0 = No; 1 = Yes
R/W
INT
R44278I
G4_BLOCKZ3
BLOCKZ3
0 = No; 1 = Yes
R/W
INT
R44279I
G4_BLOCKZ4
BLOCKZ4
0 = No; 1 = Yes
R/W
INT
R44280I
G4_USE_OST
USE_OST
0 = No; 1 = Yes
R/W
INT
R44281I
G4_NUMBRCHAR
NUMBRCHAR
2, 3
R/W
INT
R44282I
G4_TRIPIN_OUT
TRIPIN_OUT
0 = IN; 1 = OUT
R/W
INT
R44283F
G4_FWDREACH
FWDREACH
0.1 to 75.0
Ω
step 0.1 (5A)
0.5 to 375.0
Ω
step 0.5 (1A)
R/W
Float
R44285F
G4_REVREACH
REVREACH
0.1 to 75.0
Ω
step 0.1 (5A)
0.5 to 375.0
Ω
step 0.5 (1A)
R/W
Float
R44287I
G4_OUTER
OUTER
40 to 165° step 1
R/W
INT
R44288I
G4_MIDDLE
MIDDLE
40 to 165° step 1
R/W
INT
R44289I
G4_INNER
INNER
40 to 165° step 1
R/W
INT
R44290I
G4_TLOS1PU
TLOS1PU
1 to 100 msec. step 1
R/W
INT
R44291I
G4_TLOS1DO
TLOS1DO
1 to 100 msec. step 1
R/W
INT
R44292I
G4_TLOS2PU
TLOS2PU
1 to 100 msec. step 1
R/W
INT
R44293I
G4_TLOS3PU
TLOS3PU
1 to 100 msec. step 1
R/W
INT
R44294I
G4_TLOS4PU
TLOS4PU
1 to 100 msec. step 1
R/W
INT
R44295I
G4_RECLMODE
RECLMODE
0 = Off; 1 = None; 2 = Internal;
3 = External; 4 = Both
R/W
INT
R44296I
G4_RECLOSETYPE
RECLOSETYPE
0 = 1POLE; 1 = 3 POLE;
2 = 1POLE3POLE
R/W
INT
R44297I
G4_NUM_1P_AT
NUM_1P_AT
1, 2, 3, 4
R/W
INT
R44298F
G4_1PDELAY1
1PDELAY1
0.1 to 300.0 sec. step 0.1
R/W
Float
R44300F
G4_1PDELAY2
1PDELAY2
0.1 to 300.0 sec. step 0.1
R/W
Float
R44302F
G4_1PDELAY3
1PDELAY3
0.1 to 300.0 sec. step 0.1
R/W
Float
R44304F
G4_1PDELAY4
1PDELAY4
0.1 to 300.0 sec. step 0.1
R/W
Float
R44306I
G4_NUM_3P_AT
NUM_3P_AT
1, 2, 3, 4
R/W
INT
R44307F
G4_3PDELAY1
3PDELAY1
0.1 to 300.0 sec. step 0.1
R/W
Float
R44309F
G4_3PDELAY2
3PDELAY2
0.1 to 300.0 sec. step 0.1
R/W
Float
R44311F
G4_3PDELAY3
3PDELAY3
0.1 to 300.0 sec. step 0.1
R/W
Float
R44313F
G4_3PDELAY4
3PDELAY4
0.1 to 300.0 sec. step 0.1
R/W
Float
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 25 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...