B-
14
LPS-D Line Protection System
GE Power Management
B.1 MEMORY MAPPING
APPENDIX B
B
R43570I
G2_50_DIRCNL
50_DIRCNL
0 = No; 1 = Yes
R/W
INT
R43571F
G2_50PICKUP
50PICKUP
2.0 to 160.0 A step 0.1 (5A)
0.4 to 32.0 A step 0.1 (1A)
R/W
Float
R43573F
G2_50PICKUPFF
50PICKUPFF
2.0 to 160.0 A step 0.1 (5A)
0.4 to 32.0 A step 0.1 (1A)
R/W
Float
R43575I
G2_50G
50G
0 = No; 1 = Yes
R/W
INT
R43576I
G2_50G_DIRCNL
50G_DIRCNL
0 = No; 1 = Yes
R/W
INT
R43577F
G2_50GPICKUP
50GPICKUP
0.5 to 80.0 A step 0.1 (5A)
0.1 to 16.0 A step 0.1 (1A)
R/W
Float
R43579F
G2_50GPICKUPFF
50GPICKUPFF
0.5 to 80.0 A step 0.1 (5A)
0.1 to 16.0 A step 0.1 (1A)
R/W
Float
R43581F
G2_50GRESTNT
50GRESTNT
0.0, 0.3
R/W
INT
R43583I
G2_51G
51G
0 = No; 1 = Yes
R/W
INT
R43584I
G2_51G_DIRCNL
51G_DIRCNL
0 = No; 1 = Yes
R/W
INT
R43585F
G2_51GPICKUP
51GPICKUP
0.20 to 15.0 A step 0.01 (5A)
0.04 to 3.0 A step 0.01 (1A)
R/W
Float
R43587F
G2_51GPICKUPFF
51GPICKUPFF
0.20 to 15.0 A step 0.01 (5A)
0.04 to 3.0 A step 0.01 (1A)
R/W
Float
R43589I
G2_51GCURVE
51GCURVE
0 = INV; 1 = V-INV; 2 = EINV;
3 = CUSTOM; 4 = DEFT
R/W
INT
R43590F
G2_51GTIMDIAL
51GTIMDIAL
0.5 to 10.0 step 0.1
R/W
Float
R43592F
G2_51GDEFTIMDELY
51GDEFTIMDELY
0.5 to 30 sec. step 0.1
R/W
Float
R43594I
G2_51G_RESET
51G_RESET
0 = FAST; 1 = EM
R/W
INT
R43595I
G2_RATEDVOLTS
RATEDVOLTS
1.14 V
R/W
INT
R43596I
G2_PHASEOVER
PHASEOVER
0 = No; 1 = Yes
R/W
INT
R43597F
G2_PHOVPICKUP
PHOVPICKUP
0.0 to 1.4 p.u. V step 0.01
R/W
Float
R43599F
G2_PHOVTMDLY
PHOVTMDLY
0.0 to 10.0 sec. step 0.01
R/W
Float
R43601I
G2_V1OVER
V1OVER
0 = No; 1 = Yes
R/W
INT
R43602F
G2_V1OVINSTPU
V1OVINSTPU
1.0 to 1.4 p.u. V step 0.01
R/W
Float
R43604F
G2_V1OVTIMPU
V1OVTIMPU
1.0 to 1.4 p.u. V step 0.01
R/W
Float
R43606F
G2_V1OVTIMDLY
V1OVTIMDLY
0.0 to 10.0 sec. step 0.01
R/W
Float
R43608I
G2_V1COMP
V1COMP
0 = No; 1 = Yes
R/W
INT
R43609F
G2_V1COMRCH
V1COMRCH
0.01 to 50.0
Ω
step 0.01 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
R43611F
G2_VICOMPINPU
V1COMPINPU
1.0 to 1.4 p.u. V step 0.01
R/W
Float
R43613F
G2_V1COMPTDPU
V1COMPTDPU
1.0 to 1.4 p.u. V step 0.01
R/W
Float
R43615F
G2_V1COMPDLY
V1COMPDLY
0.0 to 10.0 sec. step 0.01
R/W
Float
R43617I
G2_FUSEFAIL
FUSEFAIL
0 = No; 1 = Yes
R/W
INT
R43618I
G2_ALL_BELOW
ALL_BELOW
0 = No; 1 = Yes
R/W
INT
R43619I
G2_OUTOFSTEP
OUTOFSTEP
0 = No; 1 = Yes
R/W
INT
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 10 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...