LPS-D Line Protection System
GE Power Management
B.1 MEMORY MAPPING
APPENDIX B
B
R43851I
G3_Z4TIMERS
Z4TIMERS
0 = No; 1 = Yes
R/W
INT
R43852F
G3_Z4P_TIME
Z4P_TIME
0.10 to 10.0 sec. step 0.01
R/W
Float
R43854F
G3_Z4G_TIME
Z4G_TIME
0.10 to 10.0 sec. step 0.01
R/W
Float
R43856F
G3_IT_PICKUP
IT_PICKUP
0.20 to 4.0 A step 0.01 (5A)
0.04 to 0.8 A step 0.01 (1A)
R/W
Float
R43858F
G3_IB_PICKUP
IB_PICKUP
0.20 to 4.0 A step 0.01 (5A)
0.04 to 0.8 A step 0.01 (1A)
R/W
Float
R43860F
G3_IPT_PICKUP
IPT_PICKUP
0.50 to 5.0 A step 0.01 (5A)
0.1 to 1.0 A step 0.01 (1A)
R/W
Float
R43862F
G3_IPB_PICKUP
IPB_PICKUP
0.25 to 3.75 A step 0.01 (5A)
0.05 to 0.75 A step 0.01 (1A)
R/W
Float
R43864F
G3_IPBKFACTOR
IPBKFACTOR
0.0, 0.066
R/W
Float
R43866F
G3_NT_OFFSET
NT_OFFSET
0.0 to 20.0 W step 0.01
0.0 to 100 W step 0.01
R/W
Float
R43868I
G3_UNBALALARM
UNBALALARM
0 = No; 1 = Yes
R/W
INT
R43869I
G3_50
50
0 = No; 1 = Yes
R/W
INT
R43870I
G3_50_DIRCNL
50_DIRCNL
0 = No; 1 = Yes
R/W
INT
R43871F
G3_50PICKUP
50PICKUP
2.0 to 160.0 A step 0.1 (5A)
0.4 to 32.0 A step 0.1 (1A)
R/W
Float
R43873F
G3_50PICKUPFF
50PICKUPFF
2.0 to 160.0 A step 0.1 (5A)
0.4 to 32.0 A step 0.1 (1A)
R/W
Float
R43875I
G3_50G
50G
0 = No; 1 = Yes
R/W
INT
R43876I
G3_50G_DIRCNL
50G_DIRCNL
0 = No; 1 = Yes
R/W
INT
R43877F
G3_50GPICKUP
50GPICKUP
0.5 to 80.0 A step 0.1 (5A)
0.1 to 16.0 A step 0.1 (1A)
R/W
Float
R43879F
G3_50GPICKUPFF
50GPICKUPFF
0.5 to 80.0 A step 0.1 (5A)
0.1 to 16.0 A step 0.1 (1A)
R/W
Float
R43881F
G3_50GRESTNT
50GRESTNT
0.0, 0.3
R/W
INT
R43883I
G3_51G
51G
0 = No; 1 = Yes
R/W
INT
R43884I
G3_51G_DIRCNL
51G_DIRCNL
0 = No; 1 = Yes
R/W
INT
R43885F
G3_51GPICKUP
51GPICKUP
0.20 to 15.0 A step 0.01 (5A)
0.04 to 3.0 A step 0.01 (1A)
R/W
Float
R43887F
G3_51GPICKUPFF
51GPICKUPFF
0.20 to 15.0 A step 0.01 (5A)
0.04 to 3.0 A step 0.01 (1A)
R/W
Float
R43889I
G3_51GCURVE
51GCURVE
0 = INV; 1 = V-INV; 2 = EINV;
3 = CUSTOM; 4 = DEFT
R/W
INT
R43890F
G3_51GTIMDIAL
51GTIMDIAL
0.5 to 10.0 step 0.1
R/W
Float
R43892F
G3_51GDEFTIMDELY
51GDEFTIMDELY
0.5 to 30 sec. step 0.1
R/W
Float
R43894I
G3_51G_RESET
51G_RESET
0 = FAST; 1 = EM
R/W
INT
R43895I
G3_RATEDVOLTS
RATEDVOLTS
1.14 V
R/W
INT
R43896I
G3_PHASEOVER
PHASEOVER
0 = No; 1 = Yes
R/W
INT
R43897F
G3_PHOVPICKUP
PHOVPICKUP
0.0 to 1.4 p.u. V step 0.01
R/W
Float
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 16 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...