2-
20
LPS-D Line Protection System
GE Power Management
2.3 PROTECTION SETTINGS
2 CALCULATION OF SETTINGS
2
•
Step Distance and POTT1 Schemes
If the Zone 4 phase distance functions are to be used to provide time-delayed backup protection, then set
Z4PHASE = YES; otherwise, set Z4PHASE = NO.
402: Z4PHREACH - Zone 4 Phase Distance Reach
•
Blocking, Hybrid and POTT2 Schemes
In a blocking scheme, the Zone 4 functions key the transmitter to send a blocking signal to the remote ter-
minal of the line to block tripping for an external fault (F1, for example) within reach of the Zone 2 functions
located at the remote terminal.
In a hybrid scheme, the Zone 4 functions prevent keying of the transmitter to block echoing of the trip sig-
nal that was received as a result of the operation of the remote Zone 2 functions for an external fault (at F1
for example) within their reach.
In a POTT2 scheme the Zone 4 functions establish transient blocking circuitry to prevent tripping during
fault clearing and fault current reversals.
In all of these schemes, it is therefore imperative that blocking functions be set with a reach that will allow
them to see all faults that the remote Zone 2 functions will see. The following guidelines are proposed:
1.
If the reach of the Zone 2 phase distance function (Z2PHREACH
R
) at the remote end of the line is less
than twice the positive-sequence impedance of the line, then the proposed setting is:
Z4PHREACH = 0.85 x Z2PHREACH
R
2.
If the reach of the Zone 2 functions at the remote end is greater than twice the positive-sequence
impedance of the line, then the proposed settings are:
Z4PHREACH = 1.7 x (Z2PHREACH
R
-
Z
1
L
)
where:
Z2PHREACH
R
= reach of phase Zone 2 functions at remote line terminal
Z
1
L
= positive sequence impedance of protected line
With these proposed settings, proper coordination will be obtained between the tripping and blocking func-
tions at the remote terminal of the line. It may be possible to use a shorter setting or a longer setting than
proposed, but,
1.
If a longer setting is used, the reach should be checked per the maximum allowable reach procedure
given under Section 2.3.2: ZONE 2, 3, AND 4 DISTANCE FUNCTIONS on page 2–13. See Figure 2–
4: MAXIMUM ALLOWABLE REACH on page 2–13.
2.
If a shorter reach setting is used, then the reach should be checked to assure that the function will
operate for all faults that the remote Zone 2 function can operate for.
When series capacitors are used on the protected line or in lines adjacent to the protected line, set the
Zone 4 phase distance functions with a reach that is equal to or greater than the reach of the phase dis-
tance pilot tripping functions (normally Zone 2) at the remote end of the transmission line. For example:
Z4PHREACH
≥
Z2PHREACH
R
where Z2PHREACH
R
is the reach of the pilot tripping functions (Zone 2 in this example) at the remote end
of the line.
•
Step Distance and POTT2 Schemes
In all other schemes, the Zone 4 phase distance functions can provide an additional zone of time-delayed
backup protection. They can be used to provide a fourth zone of protection in a straight Step Distance
scheme, or they can be reversed in direction to provide the so-called “reversed third zone” of protection.
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...