GE Power Management
LPS-D Line Protection System
12-
5
12 ASCII COMMUNICATIONS
12.1 INTRODUCTION
12
GROUP
SETTING
The active Protectioning Setting Group number is 1
To select a Setting Group enter Setting Group
Number (‘1’ - ‘4’)
To select active setting group through Contact
Converter Inputs enter ‘0’
To quit press ESC
Enter your choice:
Are you sure (Y/N):? y
New Active Group = 3
Enter digit from
0 to 4; enter
letter
INPuts
Request contact converter
status
VIEW
Contact Converter #0=0 (SETTING GROUP BIT 0)
Contact Converter #1=1 (SETTING GROUP BIT 1)
Contact Converter #2=1
(not assigned)
Contact Converter #3=0
(not assigned)
Contact Converter #4=0
(not assigned)
Contact Converter #5=1
(not assigned)
Contact Converter #6=0
(not assigned)
Contact Converter #7=1
(not assigned)
None
MODEL
Retrieve the model
number, serial number,
and version of the relay
VIEW
MODEL: LPSDA35U143VE3S
VERSION: V0001.11
None
CRCcalc
Recalculates the CRC of
various settings groups
(this is primarily a
troubleshooting command
- it is used only where a
relay may have gone
through a loss power
during a settings change,
and the settings are
corrupted beyond the
ability of the relay to
correct).
SETTINGS
CRCs are recalculated
None
STLINID
Allows the station and line
IDs to be changed
SETTINGS
Station ID: Current Station ID
Line ID: Current Line ID
Do you want to change Station and/or
Line ID? (Y/N): y
Enter new Station ID (max. 32 characters): NEW
STATION ID
Enter new Line ID (max. 32 characters): NEW
FEEDER ID
Are you sure? (Y/N): y
Y to change, N
to exit; NEW
STATION ID or
ENTER to keep
current ID; NEW
FEEDER ID or
ENTER to keep
current ID; enter
letter
Table 12–3: ASCII COMMAND LIST (Sheet 4 of 7)
ASCII
Command
Mnemonic
Command Description
Lowest
Level
Password
Needed
Relay Prompt
User Response
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...