3-
6
LPS-D Line Protection System
GE Power Management
3.3 PRINTED CIRCUIT BOARD MODULES
3 HARDWARE DESCRIPTION
3
3.3 PRINTED CIRCUIT BOARD MODULES
3.3.1 WARNING
This relay contains electronic components that can be damaged by electrostatic discharge
currents. The main source of electrostatic discharge currents is the human body, and low
humidity, carpeted floors, and isolating shoes are conducive to the generation of electrostatic
discharge currents. Care should be exercised when removing and handling the modules.
Each person handling the printed circuit boards must ensure that their body through a
grounding wrist strap or similar apparatus tied to ground potential
before
touching any of the
components on the boards or the boards themselves.
The printed-circuit boards are located inside the case in the positions shown in Figure 3–3: CIRCUIT BOARD
LOCATIONS on page 3–3.
3.3.2 BASIC CONSTRUCTION
Each module consists of a printed-circuit board and aluminum plate. The printed circuit board is securely
mounted to five stand-offs on the plate with five screws. There are two tabs on the front of the aluminum plate
for removing and inserting the module. Electrical connection is made by an edge connector on the rear of the
input and output boards and ribbon cables and the bus card connector on the front of the boards.
3.3.3 MODULE IDENTIFICATION
Each module is identified by silk screen description on the printed circuit board.
Power down the relay by removing any DC voltage to the relay before removing or inserting
modules. Failure to do so can permanently damage the relay.
3.3.4 LOCAL USER INTERFACE (LUI)
The Keypad / Display Interface contains a 4-line, 20-character LED display, a green/red status LED, a red trip
LED, a 9-pin RS232 port, and the 20-character keypad. The interface logic is contained on two printed circuit
boards (DSP/ANI and LUI).
•
LUI module board contains all of the items listed above except the keyboard decoding logic which is on the
DSP/ANI board.
•
The Output board contains the LPS-D communications interface (RS232 / ASCII), a Critical Alarm Timer,
various output relay drivers, and user-selectable switches to enable remote functions.
3.3.5 INPUT BOARD
The input board contains the input logic which includes the programmable contact converter optocouplers. The
SCADA I/V (current/voltage) selection switch, SW1, is in the back, left corner on this board. The IRIG-B input is
also on this board. Figure 3–5: INPUT BOARD DIAGRAM is the block diagram of the input board.
CAUTION
CAUTION
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...