B-
28
LPS-D Line Protection System
GE Power Management
B.1 MEMORY MAPPING
APPENDIX B
B
R44229I
G4_BYPASSTL3
BYPASSTL3
0 = No; 1 = Yes
R/W
INT
R44230F
G4_I1PICKPU
I1PICKUP
1.0 to 15.0 A step 0.1
0.2 to 3.0 A step 0.1
R/W
Float
R44232I
G4_REMOTEOPEN
REMOTEOPEN
0 = No; 1 = Yes
R/W
INT
R44233I
G4_TL20PICKUP
TL20PICKUP
10 to 100 msec. step 1
R/W
INT
R44234I
G4_LINEOVERLD
LINEOVERLD
0 = No; 1 = Yes
R/W
INT
R44235F
G4_LEVEL1PU
LEVEL1PU
2.5 to 20.0 A step 0.1 (5A)
0.5 to 4.0 A step 0.1 (1A)
R/W
Float
R44237F
G4_LEVEL2PU
LEVEL2PU
5.0 to 40.0 A step 0.1 (5A)
1.0 to 8.0 A step 0.1 (1A)
R/W
Float
R44239F
G4_LEVEL1TDLY
LEVEL1TDLY
10 to 200 sec. step 1
R/W
Float
R44241F
G4_LEVEL2TDLY
LEVEL2TDLY
10 to 99 sec. step 1
R/W
Float
R44243I
G4_PICKSCHEME
PICKSCHEME
0 = STEPDST; 1 = PUTT;
2 = POTT1; 3 = POTT2;
4 = HYBRID
R/W
INT
R44244I
G4_NUMRCVR
NUMRCVR
0, 1, 2
R/W
INT
R44245I
G4_TRIPMODE
TRIPMODE
0 = 3POLE; 1 = 1POLE;
2 = 1POLEZ2
R/W
INT
R44246I
G4_CARRSTART
CARRSTART
0 = DIR; 1 = IPB; 2 = FD
R/W
INT
R44247I
G4_WKINFTRIP
WKINFTRIP
0 = No; 1= Yes
R/W
INT
R44248I
G4_TL1PICKUP
TL1PICKUP
1 to 200 msec. step 1
R/W
INT
R44249I
G4_TL4PICKUP
TL4PICKUP
0 to 50 msec. step 1
R/W
INT
R44250I
G4_TL4DROPOUT
TL4DROPOUT
0 to 50 msec. step 1
R/W
INT
R44251I
G4_TL5PICKUP
TL5PICKUP
0 to 200 msec. step 1
R/W
INT
R44252I
G4_TL5DROPOUT
TL5DROPOUT
0 to 200 msec. step 1
R/W
INT
R44253I
G4_TL6PICKUP
TL6PICKUP
0 to 200 msec. step 1
R/W
INT
R44254I
G4_TL6DROPOUT
TL6DROPOUT
0 to 200 msec. step 1
R/W
INT
R44255I
G4_TL16PICKUP
TL16PICKUP
8 to 99 msec. step 1
R/W
INT
R44256I
G4_TL24DROPOUT
TL24DROPOUT
30 to 500 msec. step 1
R/W
INT
R44257I
G4_TL25DROPOUT
TL25DROPOUT
30 to 500 msec. step 1
R/W
INT
R44258I
G4_TL26PICKUP
TL26PICKUP
0 to 50 msec. step 1
R/W
INT
R44259I
G4_POSSEQANG
POSSEQANG
25 to 90° step 1
R/W
INT
R44260I
G4_ZERSEQANG
ZERSEQANG
25 to 90° step 1
R/W
INT
R44261F
G4_ZLINE
ZLINE
0.01 to 50
Ω
step 0.01
0.05 to 250
Ω
step 0.05
R/W
Float
R44263F
G4_ZEROSEQK0
G4_ZEROSEQK0
1.0 to 7.0 step 0.1
R/W
Float
R44265F
G4_LINELENGTH
LINELENGTH
0.0 to 500.0 step 0.1
R/W
Float
R44267I
G4_LINEUNIT
LINEUNIT
0 = Miles, 1 = Km
R/W
INT
R44268I
G4_CTRATIO
CTRATIO
1 to 5000 step 1
R/W
INT
R44269I
G4_PTRATIO
PTRATIO
1 to 7000 step 1
R/W
INT
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 24 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...