Medium connection
42
Additional valves
Connect the additional valves as follows:
You can use the additional valves for "Sealing water" for example.
The valves are assigned in "Set up 2 > Topcal > Config. Topcal".
Activate the sealing water in "Set up 2 > Topcal > Activate Topcal".
What is sealing water?
In processes where the medium is fibrous or tends to stick, assemblies with a ball valve for shutting
off the medium are used e.g. Cleanfit P CPA473 or CPA474. To keep the rinse chamber free of
medium, the sealing water valve opens automatically before the assembly moves out of the process.
The counterpressure in the rinse chamber caused by the sealing water prevents the ingress of
medium into the chamber. The sealing water pressure must then be greater than the pressure of the
medium. The time the sealing water runs before and after moving the assembly can be set
individually.
5.2
Water pipe and rinse chamber
a0006201
Fig. 45:
Connecting rinsing block to rinse chamber and water connection
1
Rinse water
2
Rinsing block, rinse chamber connection
3
Assembly, rinse chamber connection
4
Water filter
5
Water connection
Connecting the rinse chamber
Connect the rinse chamber connection at the rinsing block (2) to the rinse connection of the
assembly (3).
Valve number
Function
V1
Control of additional valve 1 for sealing water etc.
V2
Control of additional valve 2 for sealing water etc.
1
4
5
2
3