Wiring
24
Control unit power supply
1.
Guide the voltage cable through a suitable Pg gland and into the control unit housing.
2.
Connect the green/yellow core to the PE terminal.
3.
Connect the two other cable cores to terminals "L+" and "N-" (bottom terminal block, left).
Communication connection between Mycom and control unit
1.
Guide the end of the communication cable with the black shield wire through a suitable Pg
gland on Mycom.
2.
Guide the other end of the communication cable through a Pg gland on the control unit.
3.
Connect the cable cores as follows:
4.1.5
Level probes for buffer and cleaner
a0005835
Fig. 21:
Connecting level probes for buffer and cleaner
A
Cleaner
B
Buffer 1
C Buffer
2
Cable core
Mycom connection
Control unit connection
Yellow (YE)
Terminal B
Terminal B
Green (GN)
Terminal A
Terminal A
White (WH)
Terminal L-
Terminal L-
Brown (BN)
Terminal L+
Terminal L+
Black (BK)
PE grounding bar
n.c.
D1 D2 P1 P2 P3 P4 P5 P6
A
B
C