Technical data
154
11
Technical data
11.1
Input
11.2
Output
Mycom S CPM153
Binary inputs E1 to E3
Input voltage:
Internal resistance:
10 ... 50 V
R
i
= 5 k
Ω
Current inputs 1 / 2
(passive optional)
Signal range:
Input voltage range:
4 ... 20 mA
6 ... 30 V
CPG310
Binary inputs
Input voltage:
Internal resistance:
Minimum switching signal
duration:
10 ... 40 V
R
i
= 5 k
Ω
500 ms
Mycom S CPM153
Output signal
0/4 ... 20 mA
Signal on alarm
2.4 or 22 mA in the event of an error
Load of active current
output
Max. 600
Ω
(depends on operating voltage)
Passive current output
Operating voltage range:
6 ... 30 V
Galvanic isolation
The following are on the same potential:
• Current output 1 and auxiliary voltage
All other circuits are galvanically isolated from one another.
Output distribution
pH:
Adjustable, 0 ... 18 pH
Redox
Absolute:
Relative:
Adjustable, 300 ... 3000 mV
Adjustable, 0 ... 600 %
Temperature:
Adjustable, 17 ... 200
°
C (62.6 ...
392
°
F)
Overvoltage protection
As per EN 61000-4-5:1995
Auxiliary voltage output
Output voltage:
Output current:
15 V DC
Max. 9 mA
Contact outputs
Switching voltage:
Switching current:
Switching power:
Operating life:
Max. 250 V AC / 125 V DC
Max. 3 A
Max. 750 VA
≥
5 million switching cycles
Controller
Function (adjustable):
Pulse-length controller (PWM)
Pulse-frequency controller (PFM)
Three-point stepping controller
(3-point step)
Analog (via current output)
Controller behavior:
Control gain K
R
:
Integral action time T
n
:
Derivative action time T
v
:
Max. frequency with pulse-frequency controller:
Period length for pulse-length controller:
Minimum switch-on period for pulse-length
controller:
P / PI / PID
0.01 … 20.00
0.0 … 999.9 min
0.0 … 999.9 min
120 min
-1
1 ... 999.9 s
0.4 s
Содержание Topcal S CPC310