Commissioning
98
Edit day
Select programs
Activation and subsequent entry
• Clean
18:22 18:23
• Interval
18:24 18:54
• No prog.
Factory setting
No prog.
Select the cleaning programs for the day and
enter the times for the start of cleaning.
If you select the interval program, also enter the
time for stopping the cleaning.
The time for start and end is always shown.
Example:
Clean
18:22 (start time) 18:23 (end time)
!
Note!
10 program starts are possible each day.
Copy day
Select day
Options
• Tuesday
• Wednesday
• Thursday
• Friday
• Saturday
• Sunday
Factory setting
Tuesday
Select the day to which you want to copy the
day previously selected (e.g. Monday).
!
Note!
Danger of data loss. When copying one day to
another, the cleaning programs of the target day
are overwritten.
Interval program
Select program
Enter interval
Activation and subsequent entry
• Program
– Clean
– Clean C
– Clean S
– Clean CS
– User 1
– User 2
– User 3
• Interval
0 ... 36000 s
Factory setting
Program: Clean
Interval: 3600 s
Program:
Select the program that should be
started at the defined intervals.
Interval:
Enter the time that should elapse
between the end of one program cycle and the
start of the next program cycle.
!
Note!
Enter an interval of at least 10 minutes here so
that the program cycles can be ended and
started correctly.
Change name
0 ... 9; A ... Z
You can enter any name for the interval
program.
Cleaning
Select program
Options
• No prog.
• Clean
• Clean C
• Clean CS
• Clean S
• User prog.
Factory setting
No prog.
Select the program that should be started if the
electrode is fouled or clogged.
Power failure program
Note
The selected program is started
after a network communication
or air supply failure
Function
Options
Info