Commissioning
101
Automatic programming:
You can program every day individually. Select "
Ñ
> Set up 2 > Chemoclean > Automatic" for this
purpose:
The following programs are available:
• Clean: Cleaning start by entering the start time.
• Interval program: Cleaning takes place at defined intervals. This program cannot be triggered
directly by means of the binary inputs.
• User: User-defined cleaning programs (create in the program editor).
Program cycles
Monday: Clean x 2 (at 11:00 and at 18:00) with water for 120 s, 60 s of which also with cleaner.
Between 18:20 and 24:00, clean every 30 min. (= 1800 s) with water for 120 s, 60 s of which also
with cleaner.
a0004955-en
Fig. 62:
Graphic representation of the above example
Necessary settings as per the example (bold: to be entered by the user):
Interval program
Hold
Hold and after-effect time
Hold and after-effect time
Interval 1800 s
Prog.
Interval 1800 s
Clean
Hold
Hold and after-effect time
Prog. 60 s
60 s
+cleaner
60 s
60 s
+cleaner
60 s
60 s
+cleaner
"Automatic > Weekday > Edit
day" field
"Edit prog. > Clean > Setup" field
"Interval program" field
Clean
01 Water
60 s
Program
Clean
11:00
11:02
02 +Cleaner
60 s
Interval
1800 s
Clean
03 Water
0 s
18:00
18:02
04 rep. clean.
0x
Interval program
18:20
23:59
Содержание Topcal S CPC310