Commissioning
86
Segmented curve
characteristic values
Activation and subsequent entry
• Start neutral zone
-2.00 ... 7.00 pH
• End neutral zone
7.00 ... 16.00 pH
• Control point
-2.00 ... 16.00 pH (depends
on start neutral and end
neutral zone)
• Opt. pt. X1
2.00 ... 7.00 pH (depends on
start neutral zone)
• Opt. pt. Y1
00.00 ... 99.99
• Opt. pt. X2
7.00 ... 16.00 pH (depends on
end neutral zone)
• Opt. pt. Y2
00.00 ... 99.99
• Control point 1
2.00 ... 7.00 pH (depends on
opt. pt. X1)
• Control point 2
7.00 ... 16.00 pH (depends on
opt. pt. X2)
Factory setting
Start neutral zone: 6.50 pH
End neutral zone: 7.50 pH
Control point: 7.00 pH
Opt. pt X1: 05.00 pH
Opt. pt Y1: 0.20
Opt. pt X2: 09.00 pH
Opt. pt Y2: -0.20
Control point 1: 02.00 pH
Control point 2: 12.00 pH
Enter the characteristic values for
range-dependent control gain.
Control point:
The value that is to be set.
Start neutral zone:
Start neutral zone
End neutral zone:
End neutral zone
Optimization point 1 and 2:
Entry with x
and y coordinates
Control point 1:
For measured values <
control point 1, the dosing is 100% base.
Control point 2:
For measured values >
control point 2, the dosing is 100% acid.
Parameter
Activation and subsequent entry
• Tn 1
000.0 ... 999.9
• Tn 2
000.0 ... 999.9
• Tv 1
000.0 ... 999.9
• Tv 2
000.0 ... 999.9
Factory setting
Tn 1: 000.0
Tn 2: 000.0
Tv 1: 000.0
Tv 2: 000.0
Enter the parameters for the segmented curve.
(Index 1 only for base dosing, index 2 only for
acid dosing)
Tn:
Integral action time
Tv:
Derivative action time
Controller simulation
Options
• On
• Off
Factory setting
Off
Here, you can switch a configuration loop on or
off. Hold is taken away when controller
simulation is activated.
Simulation on:
The characteristic values
entered in the previous field are used in the
next field for simulating the controller behavior.
Off:
Controller simulation is exited when you
confirm with
F
.
Function
Options
Info