Commissioning
84
2 outputs
Control type
Activation and subsequent entry
• Acid
– Pulse length
– Pulse frequency
• Base
– Pulse length
– Pulse frequency
Factory setting
Acid: Pulse length
Base: Pulse length
Select the type of control for your process.
!
Note!
Detailed information on the types of control is
provided on the CD-ROM D+.
For acid/base dosing in each
case:
Actuator (only for pulse
length)
Activation and subsequent entry
• Relay:
n.c., rel. x
• Period
001.0 ... 999.9 s
• Min. on time
000.4 ... 100.0 s
Factory setting
Relay: n.c.
Period: 010.0 s
Min. on time: 000.4 s
Select the settings for the actuator.
Relay:
Select the relay; you can choose from
the relays that you assigned to the controller in
"Set up 1 - Relays".
Period:
Period length T in seconds
Min. on time:
Minimum switch-on time;
shorter pulses are not passed on to the relay and
thus protect the actuator.
For acid/base dosing in each
case:
Actuator (only for pulse
frequency)
Activation and subsequent entry
• Relay:
n.c., rel. x
• Max. frequency
060 ... 120 min
-1
Factory setting
Relay: n.c.
Max. frequency: 120 min
-1
Select the settings for the actuator.
Relay:
Select the relay; you can choose from
the relays that you assigned to the controller in
"Set up 1 - Relays".
Max. pulse frequency:
Enter the maximum
pulse frequency; pulses with a higher frequency
are not passed on to the relay.
Characteristic
Characteristic type
Options
• Linear
• Segmented
Select the characteristic type.
Linear characteristic
Corresponds to a
constant control gain.
Segmented characteristic
Corresponds to a
range-dependent control gain.
Linear curve
characteristic values
Activation and subsequent entry
• Start neutral zone
-2.00 ... 7.00 pH
• End neutral zone
7.00 ... 16.00 pH
• Control point
-2.00 ... 16.00 pH (depends
on start neutral and end
neutral zone)
• K
R
1
00.00 ... 99.99
• K
R
2
00.00 ... 99.99
Factory setting
Start neutral zone: 6.50 pH
End neutral zone: 7.50 pH
Control point: 7.00 pH
K
R
1: 01.00
K
R
2: 01.00
Select the settings for linear control gain.
Control point:
The value that is to be set.
Start neutral zone:
Start neutral zone
End neutral zone:
End neutral zone
K
R
1
(only for base dosing): Gain for base
dosing
K
R
2
(only for acid dosing): Gain for acid dosing
Function
Options
Info