Commissioning
Proline Promag H 500 PROFIBUS DP
114
Hauser
Terminal number
Active level
Terminal number
Response time status input
Terminal number
Parameter overview with brief description
Parameter
Description
User interface / Selection /
User entry
Factory setting
Terminal number
Shows the terminal numbers used by the
status input module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• 20-21 (I/O 4)
–
Assign status input
Select function for the status input.
• Off
• Reset totalizer 1
• Reset totalizer 2
• Reset totalizer 3
• Reset all totalizers
• Flow override
Off
Active level
Define input signal level at which the
assigned function is triggered.
• High
• Low
High
Response time status input
Define the minimum amount of time the
input signal level must be present before the
selected function is triggered.
5 to 200 ms
50 ms
10.6.8 Configuring the current output
The
Current output
wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output
‣
Current output 1 to n
Terminal number
Signal mode
Assign current output 1 to n
Current span
0/4 mA value
20 mA value