System integration
Proline Promag H 500 PROFIBUS DP
92
Hauser
9.2.1
Manufacturer-specific GSD
This GSD guarantees the unrestricted functionality of the measuring device. Device-specific
process parameters and functions are therefore available.
Manufacturer-specific GSD
ID number
File name
PROFIBUS DP
0x1570
EH3x1570.gsd
The fact that the manufacturer-specific GSD should be used is specified in the
Ident
number selector
parameter by selecting the
Manufacturer
option.
Where to acquire the manufacturer-specific GSD:
→ Downloads area
9.2.2
Profile GSD
Differs in terms of the number of Analog Input blocks (AI) and the measured values. If a
system is configured with a Profile GSD, it is possible to exchange devices made by
different manufacturers. However, it is essential to ensure that the order of the cyclic
process values is correct.
ID number
Supported blocks
Supported channels
0x9740
• 1 Analog Input
• 1 Totalizer
• Channel Analog Input: volume flow
• Channel totalizer: volume flow
0x9741
• 2 Analog Input
• 1 Totalizer
• Channel Analog Input 1: volume flow
• Channel Analog Input 2: mass flow
• Channel totalizer: volume flow
0x9742
• 3 Analog Input
• 1 Totalizer
• Channel Analog Input 1: volume flow
• Channel Analog Input 2: mass flow
• Channel Analog Input 3: corrected volume
flow
• Channel totalizer: volume flow
The Profile GSD that is to be used is specified in the
Ident number selector
parameter by
selecting the
Profile 0x9740
option,
Profile 0x9741
option or
Profile 0x9742
option.
9.3
Compatibility with earlier model
If the device is replaced, the Promag 500 measuring device supports the compatibility of
the cyclic data with previous models. It is not necessary to adjust the engineering
parameters of the PROFIBUS network with the Promag 500 GSD file.
Earlier models:
• Promag 50 PROFIBUS DP
– ID No.: 1546 (hex)
– Extended GSD file: EH3x1546.gsd
– Standard GSD file: EH3_1546.gsd
• Promag 53 PROFIBUS DP
– ID No.: 1526 (hex)
– Extended GSD file: EH3x1526.gsd
– Standard GSD file: EH3_1526.gsd
9.3.1
Automatic identification (factory setting)
The Promag 500 PROFIBUS DP automatically recognizes the measuring device configured
in the automation system (Promag 50 PROFIBUS DP or Promag 53 PROFIBUS DP) and
Содержание Proline Promag H 500