Electrical connection
Proline Promag H 500 PROFIBUS DP
36
Hauser
Signal damping
Max. 9 dB over the entire length of the cable cross-section
Shield
Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.
For further information on planning and installing PROFIBUS networks see:
Operating Instructions "PROFIBUS DP/PA: Guidelines for planning and commissioning"
(BA00034S)
Current output 0/4 to 20 mA
Standard installation cable is sufficient.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Relay output
Standard installation cable is sufficient.
Current input 0/4 to 20 mA
Standard installation cable is sufficient.
Status input
Standard installation cable is sufficient.
Cable diameter
• Cable glands supplied:
M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in)
• Spring-loaded terminals: Suitable for strands and strands with ferrules.
Conductor cross-section 0.2 to 2.5 mm
2
(24 to 12 AWG).
Choice of connecting cable between the transmitter and sensor
Depends on the type of transmitter and the installation zones
Содержание Proline Promag H 500