Proline Promag H 500 PROFIBUS DP
Diagnostics and troubleshooting
Hauser
189
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
496 Status input simulation
Deactivate simulation status input
–
Measured variable status
Quality
Good
Quality substatus
Function check
Coding (hex)
0xBC to 0xBF
Status signal
C
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
497 Simulation block output
Deactivate simulation
–
Measured variable status
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
C
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
511 ISEM settings faulty
1. Check measuring period and integration
time
2. Check sensor properties
• Conductivity
• Corrected conductivity
• Density
• Electronic temperature
• Empty pipe detection
• Flow velocity
• Low flow cut off
• Mass flow
• Reference density
• Corrected volume flow
• Temperature
• Volume flow
Measured variable status
Quality
Bad
Quality substatus
Maintenance alarm
Coding (hex)
0x24 to 0x27
Status signal
C
Diagnostic behavior
Alarm
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
520 I/O 1 to n hardware configuration invalid
1. Check I/O hardware configuration
2. Replace wrong I/O module
3. Plug the module of double pulse output
on correct slot
–
Measured variable status
Quality
Bad
Quality substatus
Function check
Coding (hex)
0x3C to 0x3F
Status signal
F
Diagnostic behavior
Alarm