Proline Promag H 500 PROFIBUS DP
Electrical connection
Hauser
55
Potential equalization via grounding electrodes on process connection
2
1
3
4
A0028972
1
Hexagonal-headed bolts of process connection
2
Integrated grounding electrodes
3
O-ring seal
4
Sensor
7.5
Special connection instructions
7.5.1
Connection examples
PROFIBUS DP
2
1
A
B
3
4
4
A
B
A
B
A0028765
17
Connection example for PROFIBUS DP, non-hazardous area and Zone 2/Div. 2
1
Control system (e.g. PLC)
2
Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
3
Distribution box
4
Transmitter
If baud rates > 1.5 MBaud an EMC cable entry must be used and the cable shield must
continue as far as the terminal wherever possible.