Diagnostics and troubleshooting
Proline Promag H 500 PROFIBUS DP
170
Hauser
Coding
(hex)
Measuring value
Limits
Quality Substatus
Quality
Byte 5
A0032228-EN
36
Structure of the coding byte
The content of the coding byte depends on the configured failsafe mode in the particular
function block. Depending on which failsafe mode has been configured, status information
in accordance with PROFIBUS PA Profile Specification 3.02 is transmitted to the PROFIBUS
Master (Class 1) via the coding byte .
Determining the measured value status and device status via the diagnostic behavior
When the diagnostic behavior is assigned, this also changes the measured value status and
device status for the diagnostic information. The measured value status and device status
depend on the choice of diagnostic behavior and on the group in which the diagnostic
information is located.
The diagnostic information is grouped as follows:
• Diagnostic information pertaining to the sensor: diagnostic number 000 to 199
• Diagnostic information pertaining to the electronics: diagnostic number 200 to 399
• Diagnostic information pertaining to the configuration: diagnostic number 400 to 599
• Diagnostic information pertaining to the process: diagnostic number 800 to 999
Depending on the group in which the diagnostic information is located, the following
measured value status and device status are firmly assigned to the particular diagnostic
behavior:
Diagnostic information pertaining to the sensor: diagnostic number 000 to 199
Diagnostic behavior
(configurable)
Measured value status (fixed assignment)
Device diagnosis
(fixed assignment)
Quality
Quality
Substatus
Coding
(hex)
Category
(NE107)
Alarm
BAD
Maintenance
alarm
0x24 to 0x27
F
(Failure)
Maintenance
alarm
Warning
GOOD
Maintenance
demanded
0xA8 to 0xAB
M
(Maintenance)
Maintenance
demanded
Logbook entry only
GOOD
ok
0x80 to 0x8E
–
–
Off