Technical data
Proline Promag H 500 PROFIBUS DP
218
Hauser
Temperature tables
Observe the interdependencies between the permitted ambient and fluid
temperatures when operating the device in hazardous areas.
For detailed information on the temperature tables, see the separate document
entitled "Safety Instructions" (XA) for the device.
Storage temperature
The storage temperature corresponds to the operating temperature range of the
transmitter and the sensor → 25.
• Protect the measuring device against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
• Select a storage location where moisture cannot collect in the measuring device as
fungus or bacteria infestation can damage the liner.
• If protection caps or protective covers are mounted these should never be removed
before installing the measuring device.
Degree of protection
Transmitter
• As standard: IP66/67, type 4X enclosure
• When housing is open: IP20, type 1 enclosure
• Display module: IP20, type 1 enclosure
Sensor
• As standard: IP66/67, type 4X enclosure
• With the order code for "Sensor options", option
CM
: IP69 can also be ordered
External WLAN antenna
IP67
Vibration resistance
• Vibration, sinusoidal according to IEC 60068-2-6
– 2 to 8.4 Hz, 7.5 mm peak
– 8.4 to 2
000 Hz, 2 g peak
• Vibration broad-band random, according to IEC 60068-2-64
– 10 to 200 Hz, 0.01 g
2
/Hz
– 200 to 2
000 Hz, 0.003 g
2
/Hz
– Total: 2.70 g rms
Shock resistance
Shock, half-sine according to IEC 60068-2-27
6 ms 50 g
Shock resistance
Shock due to rough handling following IEC 60068-2-31
Mechanical load
• Protect the transmitter housing against mechanical effects, such as shock or impact.
• Never use the transmitter housing as a ladder or climbing aid.
Interior cleaning
• Cleaning in place (CIP)
• Sterilization in place (SIP)