Commissioning
Proline Promag H 500 PROFIBUS DP
122
Hauser
Parameter
Prerequisite
Description
Selection / User
interface / User
entry
Factory setting
Switch output function
The
Switch
option is selected
in the
Operating mode
parameter.
Select function for switch
output.
• Off
• On
• Diagnostic
behavior
• Limit
• Flow direction
check
• Status
Off
Assign diagnostic behavior
• In the
Operating mode
parameter, the
Switch
option is selected.
• In the
Switch output
function
parameter, the
Diagnostic behavior
option
is selected.
Select diagnostic behavior for
switch output.
• Alarm
• Alarm or warning
• Warning
Alarm
Assign limit
• The
Switch
option is
selected in the
Operating
mode
parameter parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter
parameter.
Select process variable for limit
function.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Conductivity
• Corrected
conductivity
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Temperature
• Electronic
temperature
Volume flow
Assign flow direction check
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Flow direction check
option is selected in the
Switch output function
parameter.
Select process variable for flow
direction monitoring.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
Volume flow
Assign status
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Status
option is
selected in the
Switch
output function
parameter.
Select device status for switch
output.
• Partially filled pipe
detection
• Low flow cut off
• Digital output 3
• Digital output 4
• Digital output 5
Partially filled pipe
detection
Switch-on value
• In the
Operating mode
parameter, the
Switch
option is selected.
• In the
Switch output
function
parameter, the
Limit
option is selected.
Enter measured value for the
switch-on point.
Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal/min (us)
Switch-off value
• In the
Operating mode
parameter, the
Switch
option is selected.
• In the
Switch output
function
parameter, the
Limit
option is selected.
Enter measured value for the
switch-off point.
Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal/min (us)
Switch-on delay
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter.
Define delay for the switch-on
of status output.
0.0 to 100.0 s
0.0 s