Commissioning
Proline Promag H 500 PROFIBUS DP
124
Hauser
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
interface / User
entry
Factory setting
Relay output function
–
Select the function for the
relay output.
• Closed
• Open
• Diagnostic
behavior
• Limit
• Flow direction
check
• Digital Output
Closed
Terminal number
–
Shows the terminal numbers
used by the relay output
module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• 20-21 (I/O 4)
–
Assign flow direction check
In the
Relay output function
parameter, the
Flow direction
check
option is selected.
Select process variable for flow
direction monitoring.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
Volume flow
Assign limit
The
Limit
option is selected in
the
Relay output function
parameter parameter.
Select process variable for limit
function.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Conductivity
• Corrected
conductivity
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Temperature
• Electronic
temperature
Volume flow
Assign diagnostic behavior
In the
Relay output function
parameter, the
Diagnostic
behavior
option is selected.
Select diagnostic behavior for
switch output.
• Alarm
• Alarm or warning
• Warning
Alarm
Assign status
In the
Relay output function
parameter, the
Digital Output
option is selected.
Select device status for switch
output.
• Partially filled pipe
detection
• Low flow cut off
• Digital output 3
• Digital output 4
• Digital output 5
Partially filled pipe
detection
Switch-off value
In the
Relay output function
parameter, the
Limit
option is
selected.
Enter measured value for the
switch-off point.
Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal(us)/min
Switch-off delay
In the
Relay output function
parameter, the
Limit
option is
selected.
Define delay for the switch-off
of status output.
0.0 to 100.0 s
0.0 s
Switch-on value
In the
Relay output function
parameter, the
Limit
option is
selected.
Enter measured value for the
switch-on point.
Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal(us)/min
Switch-on delay
In the
Relay output function
parameter, the
Limit
option is
selected.
Define delay for the switch-on
of status output.
0.0 to 100.0 s
0.0 s
Failure mode
–
Define output behavior in
alarm condition.
• Actual status
• Open
• Closed
Open
*
Visibility depends on order options or device settings