User Manual
EM303B General Purpose Inverter
155
protection and remains previous status.
FC-28~ FC-20 are bit operation. Only the corresponding bit has to be set as 0 or 1. As shown
in the table below.
FC-28 Disabled Trips 1
Fault Code
Ol
IlP
SlU
SOU
SOC
*
*
*
Bit
7
6
5
4
3
2
1
0
Value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
FC-29 Disabled Trips 2
Fault Code
EEd
EST
*
*
*
EHT
OLP
OH
Bit
7
6
5
4
3
2
1
0
Value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
FC-30Disabled Trips
3
Fault Code
*
Ol1
SOFT
SIE
SrE
SFE
STP
EEU
Bit
7
6
5
4
3
2
1
0
Value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
X
For instance: To disable Fault ILP only needs to set Bit 6 corresponding to ILP as 1, i.e.
FC-28=01000000.
To disable Fault OLP and EST only needs to set Bit 1 corresponding to OLP and Bit 6
corresponding to EST as 1, i.e. FC-29=01000010.
1. Unless special needs, please do not disable any protection function in order to
avoid that inverter is damaged if there is not fault protection when the faults occurs.
2. OL1 is motor overload. Fault display is also as OL. Generally, motor overload is
longer than inverter overload, so that the relative settings do not need to be changed.
8.14
Fd Group: Auxiliary Parameters
8.14.1
Customer Defined V/F Curve Setting
No.
Function
Range
Unit Default Type
F1-04
Frequency Base
Rated Voltage Ue
Frequency 1
Fd-05
Frequency 2
Fd-06
Frequency 3
Fd-07
Frequency 4
Fd-08
100.0%
100.0%
Voltage 1
Fd-01
Voltage 2
Fd-02
Voltage 3
Fd-03
Voltage 4
Fd-04
Frequency Base
F1-04
0requency Baseed V/F Curve Sett
Hz 50.00
〇
Fd-01
Voltage 1
% 1.00
●
Fd-02
Voltage 2
% 4.00
●
Fd-03
Voltage 3
% 10.00
●
Fd-04
Voltage 4
% 16.00
●
Fd-05
Frequency 1
% 1.00
●
Fd-06
Frequency 2
% 4.00
●
Fd-07
Frequency 3
% 10.00
●
Fd-08
Frequency 4
% 16.00
●