8.11.7
Output Frequency Range
No.
Function
Range
Unit
Default
Type
F9-11
Frequency Reach Signal FAR 0.00
~
50.00/0.0
~
50.0
Hz
2.50
〇
If
multi-function
output
or
relay
output=1(Frequency Reach Range FAR), and
if
∣
the output frequency of inverter- input
setting frequency
∣
<the setting value of
F9-11, the corresponding output terminal
will be on. See Figure 7-30 for details.
Time(S)
Time(S)
ON
ON
FAR
FAR
Output
Frequency(Hz)
Y2
0
0
Figure 7-30 Frequency Reach Range FAR
8.11.8
Output Frequency Detection Range FDT
No.
Function
Range
Unit Default Type
F9-12
FDT1 Increasing Threshold 0.00
~
Fmax /0.0
~
Fmax
Hz
30.00
〇
F9-13
FDT1 Decreasing Threshold 0.00
~
Fmax /0.0
~
Fmax
Hz
30.00
〇
F9-14
FDT2 Increasing Threshold 0.00
~
Fmax /0.0
~
Fmax
Hz
30.00
〇
F9-15
FDT2 Decreasing Threshold 0.00
~
Fmax /0.0
~
Fmax
Hz
30.00
〇
If multi-function output or relay output=2(Output Frequency Detection Range FDT1), and if
the output frequency of inverter rises to the setting value of FDT1 increasing threshold
(F9-12), the corresponding terminal will be on. If the output frequency of inverter drops and
the output frequency< the setting value of FDT1 decreasing threshold (F9-13), the
corresponding terminal will be off. See Figure 7-31-a and Figure 7-31-b.
FDT Increasing
Threshold
Time(S)
0
Y1
0
Time(S)
Output Frequency (Hz)
ON
(a)
FDT Decreasing
Threshold
FDT Decreasing
Threshold
Time(S)
0
Y1
0
Time (S)
Output Frequency
(Hz)
ON
FDT
Increasing
Threshold
ON
(b)
Figure 7-31 Output Frequency Detection Range FDT