EM303B General Purpose Inverter
105
No.
Function
Range
Unit
Default Type
F2-22
M0 Output Lower Limit
0.00
~
100.00
%
0.00
●
F2-23
M0 Output Upper Limit
0.00
~
100.00
%
100.00
●
F2-24
M0 Output Gain
0.00
~
300.00
%
95.00
●
F2-25
M1 Output Lower Limit
0.00
~
100.00
%
0.00
●
F2-26
M1Output Upper Limit
0.00
~
100.00
%
100.00
●
F2-27
M1 Output Gain
0.00
~
300.00
%
95.00
●
Upper limit/lower limit of analog output can be set to meet different meters and
requirements.
Final analog output signal= Output Lower Limit +Output gain*Analog output
variables*(Output Upper Limit- Output Lower Limit)
Analog output gain and output upper/lower limit (F2-22~F2-27) are corresponding to
terminals M0 and M1, and irrelevant to the current running status.
8.4
F3 Group: Preset Speed Operation Parameters
No.
Function
Range
Unit Default Type
F3-00
Preset Speed 1
0.00
~
Fmax/0.0
~
Fmax
Hz
0.00
●
F3-01
Preset Speed 2
0.00
~
Fmax/0.0
~
Fmax
Hz
5.00
●
F3-02
Preset Speed 3
0.00
~
Fmax/0.0
~
Fmax
Hz
10.00
●
F3-03
Preset Speed 4
0.00
~
Fmax/0.0
~
Fmax
Hz
15.00
●
F3-04
Preset Speed 5
0.00
~
Fmax/0.0
~
Fmax
Hz
20.00
●
F3-05
Preset Speed 6
0.00
~
Fmax/0.0
~
Fmax
Hz
25.00
●
F3-06
Preset Speed 7
0.00
~
Fmax/0.0
~
Fmax
Hz
30.00
●
F3-07
Preset Speed 8
0.00
~
Fmax/0.0
~
Fmax
Hz
35.00
●
F3-08
Preset Speed 9
0.00
~
Fmax/0.0
~
Fmax
Hz
40.00
●
F3-09
Preset Speed 10
0.00
~
Fmax/0.0
~
Fmax
Hz
45.00
●
F3-10
Preset Speed 11
0.00
~
Fmax/0.0
~
Fmax
Hz
50.00
●
F3-11
Preset Speed 12
0.00
~
Fmax/0.0
~
Fmax
Hz
50.00
●
F3-12
Preset Speed 13
0.00
~
Fmax/0.0
~
Fmax
Hz
50.00
●
F3-13
Preset Speed 14
0.00
~
Fmax/0.0
~
Fmax
Hz
50.00
●
F3-14
Preset Speed 15
0.00
~
Fmax/0.0
~
Fmax
Hz
50.00
●
Through preset speed control terminals and 15 preset frequency commands,EM303B can
provide 16 preset speeds by combining keypad numeric setting mode and analog setting
mode. Furthermore, it can be adjusted at any time through repeated addition analog input.
Setting Preset Speed Terminals
Terminal
No.
Default
Function
X3
F2-02
3
Preset Speed Terminal 1
X4
F2-03
4
Preset Speed Terminal 2
X5
F2-04
5
Preset Speed Terminal 3
X6
F2-05
6
Preset Speed Terminal 4
X7
F2-06
10
Inverter Fault Reset