User Manual
EM303B General Purpose Inverter
131
rcentage of analog input terminal. t.ion scale (F7-02) continuously for certain time.his
monotonic decreasing is active, the actual disabled point of ADT1=Analog ADT1 (F7-05)-
Analog ADT1 Hysteresis(F7-06), i.e. if input voltage of analog input terminal VF=2V
(10V=Analog ADT1 (og input terminal VF>2.5V (
Time(s)
VF/V
2.5
Time(s)
ADT1
Enabled
0
0
Disabled
Disabled
Hysteresis
2
Figure 7-24 ADT Function
F7-07
~
F7-10 Setting method of analog ADT2 and analog ADT3 parameters is the same as
that of analog ADT1.
8.9.3
Jog Analog Output
No.
Function
Range
Unit Default Type
F7-11
Jog M0 Output Lower Limit
0.00
~
100.00
%
0.00
●
F7-12
Jog M0 Output Upper Limit
0.00
~
100.00
%
100.00
●
F7-13
Jog M0 Output Gain
0.00
~
300.00
%
95.00
●
F7-14
Jog M1 Output Lower Limit
0.00
~
100.00
%
0.00
●
F7-15
Jog M1 Output Upper Limit
0.00
~
100.00
%
100.00
●
F7-16
Jog M1 Output Gain
0.00
~
300.00
%
95.00
●
In jog running mode, M0/M1 output can be switched as different meanings from normal
running. Analog output gain and the upper and lower limit are only for M0/M1, and not
related to present running status.
F7-14~F7-15
Jog output analog output upper limit and lower limit are for limiting the analog
output in jog running mode.
F7-16 Jog output gain is for analog output signal proportional zooming in jog running status.
8.9.4
Carrier
No.
Function
Range
Unit Default Type
F7-20
Automatic PMW
0: Disabled 1: Enabled
0
●
F7-21
Lower Limit Carrier Frequency 1.000
~
F7-22
kHz
2.000
●
F7-22
Upper Limit Carrier Frequency
0~9kW:1.000~16.000
9kW~37kW:1.000~8.000
37kW~110kW:1.000~4.000
110kW~400kW:
1.000~3.000
kHz
6.000
●