User Manual
EM303B General Purpose Inverter
88
0kW
~
9kW: carrier frequency range 1.000
~
16.000 kHz
11kW
~
37kW: carrier frequency range 1.000
~
8.000 kHz
45kW
~
110kW: carrier frequency range 1.000
~
4.000 kHz
132kW
~
400kW: carrier frequency range 1.000
~
3.000 kHz
No.
Function
Range
Unit Default Type
F0-15
Torque Boost
U
e
0
F
base
1
30
31 32 33
34
35
●
F0-15=0
Automatic torque boost
F0-15=1
~
10
Fixed torque boost curve
F0-15=11
~
20
Oil pump motor boost curve
F0-15=21
~
30
Synchronous motor boost curve
F0-15=31
~
34
Blower/water pump boost curve
F0-15=35
Customer defined V/F curve scaling (Defined via Fd-01
~
Fd-08)
No.
Function
Range
Unit Default Type
F0-16
Maximum Frequency
Fmax: 20.00
~
600.00
Hz
50.00
〇
F0-17
Upper Limit Frequency Fup: Fdown
~
Fmax
Hz
50.00
〇
F0-18
Lower Limit Frequency Fdown: 0.00
~
Fup
Hz
0.00
〇
F0-16
Fmax indicates the maximum setting frequency permitted by inverter. Range of Fmax:
20.00
~
600.00.
F0-17
Fup indicates the maximum frequency permitted to run after inverter start-up. Range of
Fup: Fdown~Fmax.
F0-18
Fdown indicates the minimum frequency permitted to run after inverter start-up.
Range of Fdown: 0.00Hz~Fup.
1. Upper limit frequency and lower limit frequency should be set prudently as per
the actual parameters listed on the nameplate of controlled motor and operational
status. Do not make the motor run for a long time in the lower frequency status.
Otherwise, the service lifespan of motor will be reduced due to overheating.
2. Correlation of maximum frequency, upper limit frequency, and lower limit frequency:
0.00Hz≤Fdown≤Fup≤Fmax≤600.00Hz
No.
Function
Range
Unit
Default
Type
F0-19
Start Mode Options
0: Normal start
1: Speed search start
0