125
status and runs as per the program operation status at power failure.
When selecting saving mode at power failure in program operation, please set
F6-01 hundreds place only, and do not set the hundreds places of F6-02~ F6-07.
8.8.3
Setting the Operation Time of Each Operation Section
No.
Function
Range
Unit
Default Type
F6-08
Operation Time T1
0.0
~
6000.0
S/min 30.0
●
F6-09
Operation Time T2
0.0
~
6000.0
S/min 30.0
●
F6-10
Operation Time T3
0.0
~
6000.0
S/min 30.0
●
F6-11
Operation Time T4
0.0
~
6000.0
S/min 30.0
●
F6-12
Operation Time T5
0.0
~
6000.0
S/min 30.0
●
F6-13
Operation Time T6
0.0
~
6000.0
S/min 30.0
●
F6-14
Operation Time T7
0.0
~
6000.0
S/min 30.0
●
F6-08~F6-14 are used to define the operation time of each operation section which can be
set within 0.0~6000.0 seconds/minutes.
When the operation time is 0 second, the time will be skipped in program operation.
Remarks:
Operation Time T=Acceleration/Deceleration time+ Steady operation time of present
section. Here acceleration/deceleration time refers to the time for the speed adjusted
when the operation started or at the end of last section.
See 7.8.1 for the time unit which is defined by the ten thousands place of F6-00.
8.8.4
Skip Frequency-To Avoid Mechanical Resonation
Setting jump frequency is for avoiding mechanical resonation. It is prohibited for inverter
running at constant speed in skip frequency range. Inverter will run smoothly if there is no
skip in acceleration or deceleration.
F6-16, F6-18, F6-20 are for setting 3 frequency skip points. Please set them as: 0.00Hz
setting 3 frequency sk.
If skip point is set as 0.00, and then skip frequency is disabled. F3-17, F3-19 and F3-211
are for setting the skip frequency range of each skip point.
No.
Function
Range
Unit Default Type
F6-16
Skip Frequency Point 1 0.00
~
600.00/0.0
~
6000.0
Hz
600.00
●
F6-17
Skip Frequency Range 1
0.00
~
20.00/0.0
~
20.0
0.00/0.0:Disabled
Hz
0.00
●
F6-18
Skip Frequency Point 2 F6-16
~
600.00/F6-16
~
6000.0 Hz
600.00
●
F6-19
Skip Frequency Range 2
0.00
~
20.00/0.0
~
20.0
0.00/0.0: Disabled
Hz
0.00
●
F6-20
Skip Frequency Point 3 F6-18
~
600.00/F6-18
~
6000.0 Hz
600.00
●
F6-21
Skip Frequency Range 3
0.00
~
20.00/0.0
~
20.0
0.00/0.0: Disabled
Hz
0.00
●