User Manual
EM303B General Purpose Inverter
92
F0-11, preset speed 1~15 (F3-00
~
F3-14), PID numeric setting F4-01, and numeric torque
current F5-12.
F0-29=2Parameter locked 1
Lock parameters except F0-29. Inverter will remain the setting before unlocked.
No.
Function
Range
Unit Default Type
F0-30
Inverter Model
0: Model G
1: Model P
0
〇
F0-30=0
Set inverter as Model G which is applicable to mechanical or constant torque load.
F0-30=1
Set inverter as Model P which is applicable to square or cubic torque load like
blower, and water pump.
★
When setting inverter as Model P, the applicable motor power refers to the Nameplate.
Note: The constant torque load is not applicable to Model P.
No.
Function
Range
Unit Default Type
F0-31
User Password
0~65535
XXXXX
〇
F0-31
sets a password to start password protection and prevent unqualified personnel from
editing the inverter parameters incorrectly. When password is 0, the password function is
disabled.
8.2
F1 Group: Motor Parameters
No.
Function
Range
Unit
Default Type
F1-00
Motor Type
0: AC induction motor
1: Not used
0
〇
F1-01
Motor Rated Power
0.40~480.00
kW
XXXX
〇
F1-02
Motor Rated Voltage
60~660
V
XXX
〇
F1-03
Motor Rated Current
0.1~1500.0
A
XXXX
〇
F1-04
Motor Rated Frequency
20.00~600.00
Hz
XXXX
〇
F1-05
Motor Rated Speed
1~60000
rpm
XXXX
〇
F1-06
Motor Wiring Mode
0:Y, 1
:
Δ
X
〇
F1-07
Motor Rated Power Factor 0.50~0.99
X
〇
F1-14
Motor Efficiency
30.0~99.0
XXX
〇
Remarks:
When connecting the inverter to the motor at the first time, please set the above parameters as
per the motor nameplate before operation.
No.
Function
Range
Unit
Default Type
F1-08
Idling Excitation Current I0
0.1~1500.0
A
XXXX
〇
F1-09
Rated Torque Current
0.1~1500.0
A
XXXX
×
F1-10
Stator Resistance R1
0.001~60.000
Ω
XXXX
〇
F1-11
Rotator Resistance R2
0.001~60.000
Ω
XXXX
〇