Inverter address code is the address code allocated to each inverter when the inverter is
connected to the computer network. Each address code is unique in this network. The
maximum number of inverter is 247 which are permitted to connect to the computer in one
network.
F1-16=0
Address code is broadcasting address.
No.
Function
Range
Unit
Default Type
F1-17
Communication Bit
Rate
0: 4800
1: 9600
2: 19200
3: 38400
bps
1
〇
F1-17=0
Communication Bit Rate: 4800bps
F1-17=1
Communication Bit Rate: 9600bps
F1-17=2
Communication Bit Rate: 19200bps
F1-17=3
Communication Bit Rate: 38400bps
No.
Function
Range
Unit
Default Type
F1-18
Communication
Parity Mode
0: No parity 1+8+1 for RTU
1: Even 8+1+1 for RTU
2: Odd parity 1+8+1+1 for RTU
0
〇
F1-18=0
No parity
F1-18=1
Even parity
F1-18=2
Odd parity
No.
Function
Range
Unit Default Type
F1-19
Master-slave
Communication Mode
0: The inverter is the slave
1: The inverter is the master
0
〇
F1-20
Receiving Address of
Slave Inverter
0:Primary Numeric Frequency F0-07
1:Auxiliary Numeric Frequency F9-06
0
〇
F1-21
Inverter Receiving
Proportion Coefficient
0.00~600.00
%
100.00
●
F1-19
Select the present inverter as the master or the slave.
F1-20
Set on the master inverter. Select the frequency setting command of slave inverter sent
by master inverter, and then send F0-07 or F9-06 to the slave inverter.
F1-21
When the inverter is the slave, (the frequency sent by master inverter* F1-21) will be
the setting numeric frequency of the slave inverter.
Remarks:
See Chapter 12 for EM303B ModBus communication protocol and examples.
No.
Function
Range
Unit
Default Type
F1-22
Analog Input Gain K1
0.00~600.00
%
100.00
●
F1-23
Analog Input Gain K2
0.00~600.00
%
0.00
●