User Manual
EM303B General Purpose Inverter
85
Forward
Stop
Reverse
RUN
Xi
F/R
COM
PLC
24V
EM303B
Inverter
f
Time
RUN
F/R
Output
Frequency
-f
Xi
(
a
)
F0
-
05=2 3-wire sequence
(
b
)
F0
-
20=0
,
F0
-
05=2
Forward/Reverse running sequence
Run
Stop
Forward/Reverse
RUN
Xi
F/R
COM
PLC
24V
EM303B
Inverter
Output
Frequency
RUN
F/R
f
-f
Xi
Time
(
c
)
F0
-
05=3 3-wire sequence
(
d
)
F0
-
20=0, F0
-
05=3
Forward/Reverse running sequence
Figure 7-3 3-Wire Sequence
Please use the buttons and switches correctly by following the mode illustrated in
the above diagrams of EM303B 3-wire sequences, otherwise, malfunctions may
occur.
No.
Function
Range
Unit Default Type
F0-06
Regular Speed
Setting Mode
0: Primary Numeric Frequency
1: VP
2: VS
3: IS
4: Not Used
5: K3*VS+K4*IS
6: K3*VS+K5*VF
7: K4*IS+K6*IF
8: MAX{K3*VS,K5*VF}
9: MAX{K4*IS,K6*IF}
10:K1*VP+K2*(K3*VS+K4*IS+K5*VF+K6*IF-K8*5V)