User Manual
EM303B General Purpose Inverter
112
Set F0-03=0 and F0-26=2, i.e. the inverter can be set as speed process PID control mode.
The control object is the speed of motor.
No.
Function
Range
Unit Default Type
F4-00
PID Regular Setting
Mode
0: Numeric PID Setting
1: VS
2: IS
3: VF
4: IF
5: VP
0
〇
F4-01
PID Numeric Setting
0.0~PID Maximum Scale
V
0.0
●
Setting Channel Options
F4-00=0
Numeric PID setting. Input PID setting value by editing F4-01 parameters through
keypad.
F4-00=1
Take input voltage of analog input terminal VS as PID setting value.
F4-00=2
Convert the input current of analog input terminal IS into the voltage, and then
take the voltage as PID setting value.
F4-00=3
Take input voltage of analog input terminal VF as PID setting value.
F4-00=4
Convert the input current of analog input terminal IF into the voltage, and then
take the voltage as PID setting value.
F4-00=5
Take VP input voltage set by keypad potentiometer as PID setting value.
PID Numeric Setting
The data of F4-01 can be directly input by keypad as PID setting value.
No.
Function
Range
Unit Default Type
F4-02
PID Feedback
Options
0: VF
1: IF
2: VS
3: IS
0
〇
PID feedback signal is input by the analog input terminal. The feedback value can be
operated mathematically based on real needs.
F4-02=0
VF input voltage is PID feedback.
F4-02=1
IF input current is PID feedback.
F4-02=2
VS input voltage is PID feedback.
F4-02=3
IS input current is PID feedback.
No.
Function
Range
Unit Default Type
F4-03
PID Maximum Scale 0.1~6000.0
10.0
●