User Manual
EM303B General Purpose Inverter
64
C0-11
7
523
C0-12
Output Current Percentage
0.00
~
300.00
%
×
524
C0-13
Effective Output Current Value 0.0
~
3000.0
A
×
525
No.
Function
Range
Unit Default Type S/N
C0-14
Output Voltage Percentage
0.00
~
200.00
%
×
526
C0-15
Effective Output Voltage Value 0.0
~
660.0
V
×
527
C0-16
DC Bus Voltage
0
~
1200
V
×
528
C0-17
Output torque percentage
0.00
~
200.00
%
×
529
C0-18
Not Used
×
530
C0-19
Program Operation Section
1
~
7
×
531
C0-20
Running Time of Present Section
of ProgramOperation
0.0
~
6000.0
S/min
×
532
C0-21
Output Power
0.0
~
3000.0
kW
×
533
C0-22
PID Input
0.0
~
PID Maximum Scale
×
534
C0-23
PID Calculation Feedback
0.00
~
PID Maximum Scale
×
535
C0-24
Torque CurrentInput I
q
*
0.00
~
200.00
%
×
536
C0-25
Torque CurrentFeedback I
q
0.00
~
200.00
%
×
537
C0-26
Input Terminal Status
X7 X6 X5 X4 X3 X2 X1
×
538
0
0
0
0
0
0
0
C0-27
Output Terminal Status
*
*
*
* R1 Y2 Y1
×
539
0
0
0
0
0
0
0
C0-28
VS Input Monitoring
0-10000
×
540
C0-29
IS Input Monitoring
0-10000
×
541
C0-30
VF Input Monitoring
0-10000
×
542
C0-31
IF Input Monitoring
0-10000
×
543
7.1.1
E0 Group: Fault Parameters
No.
Function
Range
Unit Default Type S/N
E0-00
Fault Trips
00
: No fault
SC
:
Drive Fault/OutputShortcircuit/EMC
fault
HOC
: Instantaneous overcurrent
HOU
: Instantaneous overvoltage
SOC
: Stable overcurrent
SOU
: Stable overvoltage
SlU
: Stable undervoltage/SOFT
Soft-start failure
IlP
: Input phase loss
Ol
: Inverter Overload
OL1: Motor Overload(OL &OL1
displayed as OL on the keypad)
OH
: Overheat
0
×
544