User Manual
EM303B General Purpose Inverter
146
Motor 2 Parameter Setting
8.12.3
Basic Parameters of Motor 2
No.
Function
Range
Unit Default Type
FA-14
Motor 2 Rated Power
0.40
~
480.00
kW XXXX
〇
FA-15
Motor 2 Rated Voltage
60
~
660
V
XXX
〇
FA-16
Motor 2 Rated Current
0.1
~
1500.0
A
XXXX
〇
FA-17
Motor 2 Rated Frequency
20.00
~
600.00/20.0
~
6000.0 Hz
XXXX
〇
FA-18
Motor 2 Rated Speed
1
~
60000
rpm XXXX
〇
FA-19
Motor 2 Wiring Mode
0
:
Y, 1
:
Δ
X
〇
FA-20
Motor 2 Rated Power Factor 0.50
~
0.99
X
〇
When inverter is connected to Motor 2 at the first time, please set all parameters
corresponding to the nameplate of Motor 2.
8.12.4
Motor 2 Running Parameters
No.
Function
Range
Unit Default Type
FA-21
Motor 2 Idling Excitation Current I0
0.1
~
1500.0 A
XXXX
〇
FA-22
Motor 2 Rated Torque Current
0.1
~
1500.0 A
XXXX
×
FA-23
Motor 2 Stator Resistance R1
0.01
~
60.000 Ω
XXXX
〇
FA-24
Motor 2 Rotator Resistance R2
0.01
~
60.000 Ω
XXXX
〇
FA-25
Motor 2 Stator& Rotor Leakage Inductance Ls 0.1
~
3000.0 mH XXXX
〇
FA-26
Motor 2 Stator& Rotor Mutual Inductance Lm 0.1
~
3000.0 mH XXXX
〇
FA-27
Motor 2 Efficiency
30.0
~
99.0
%
XXXX
〇
FA-21
~
FA-27
are motor parameters. Users cannot know these parameters on general
conditions, please obtain the parameters by motor parameter autotuning. Before motor
parameter autotuning, inverter will set the motor nameplate parameters, which are set by
FA-14~FA-20, as the standard motor parameters automatically.
8.13
FC Group: Parameters of Operation Control
8.13.1
Acceleration/Deceleration Mode Control
No.
Function
Range
Unit Default Type
FC-00
Acceleration/Deceleration Mode
0
:
Linear mode
1
:
S curve mode
0
〇
FC-01
Proportion of Acceleration S Curve 0.0
~
50.0
%
30.0
〇
FC-02
Proportion of Deceleration S Curve 0.0
~
50.0
%
30.0
〇
FC-00=0 Linear mode acceleration/deceleration
Output
frequency
increases/decreases
progressively
in
linear
mode.Acceleration/Deceleration time is set by F0-09 and F0-10.
FC-00=1 S curve mode acceleration/deceleration
Output frequency increases/decreases progressively as per curve. Generally S curve is used
for the applications which require smooth start and stop like elevator and conveyor. As
shown in Figure 7-23, in the process of acceleration, t1 = the setting value of FC-01*
Acceleration time, t2= the setting value of FC-02* Acceleration time. In the process of