inverter to restart from fault output stop to auto-reset. The range is 0.01
~
30.00 seconds and
can be set continuously.
FC-25
is for controlling the time for inverter to reset fault retry times. Fault occurs in running
process. After reset and restart, inverter will record the times of fault reset which have been
done. If there is no fault in the setting time of FC-25, inverter will clear the fault retry times
automatically. No fault timelag is in the range of 0.01
~
30.00 seconds and can be set
continuously.
Setting the running mode at restart
The function is controlled by F0-19.
8.13.20
Fault Type Options
No. Function
Range
Unit Default Type
FC-27
Fault
Retry
Options
*
Ol
IlP
SlU
SOU
SOC
HOU
HOC
11111111
〇
1
1
1
1
1
1
1
1
0: Fault retry permitted 1: Fault retry
prohibited
*: Not used
Fault retry control is bit operation. Only the corresponding bit has to be set as 0 or 1. As
shown in the table below.
Fault Code
*
Ol
IlP
SlU
SOU
SOC
HOU
HOC
Bit
*
6
5
4
3
2
1
0
Value
*
0/1
0/1
0/1
0/1
0/1
0/1
0/1
For instance: SOU and OL fault retry is permitted, and the other faults retries are prohibited.
Only the Bit 3 corresponding to SOU and Bit 6 corresponding to OL have to be set as 0, the
other bits are set as 1, i.e. FC-27=10110111.
8.13.21
Setting Disabled Trips
No.
Functio
n
Range
Uni
t
Default
Typ
e
FC-28
Disabled
Trips 1
Ol
IlP
SlU
SOU
SOC
*
*
*
0000000
0
〇
0
0
0
0
0
0
0
0
0: Enabled 1: Disabled *
:
Not Used
FC-29
Disabled
Trips 2
EEd
EST
*
*
*
EHT
OlP
OH
0000001
0
〇
0
0
0
0
0
0
1
0
0: Enabled 1: Disabled *
:
Not Used
FC-30
Disabled
Trips 3
*
Ol1
SOFT
SIE
SrE
SFE
STP
EEU
0000000
0
〇
0
0
0
0
0
0
0
0
0: Enabled 1: Disabled *
:
Not Used
Bit setting value=0 After detecting the fault corresponding to the bit, inverter will stop and
enter fault status.
Bit setting value=1 After detecting the fault corresponding to the bit, inverter will output