User Manual
EM303B General Purpose Inverter
141
8.11.5
Auxiliary Speed Setting Mode
No.
Function
Range
Unit Default Type
F9-05
Auxiliary Speed
Setting Mode
0: Auxiliary numeric frequency
1: VP
2: VS
3: IS
4: Not Used
5: K3*VS+K4*IS
6: K3*VS+K5*VF
7: K4*IS+K6*IF
8: MAX{K3*VS,K5*VF}
9: MAX{K4*IS,K6*IF}
10:K1*VP+K2*(K3*VS+K4*IS
+K5*VF+K6*IF-K8*5V)
0
〇
F9-06
Auxiliary Numeric
Frequency Setting
0.00
~
Fmax/0.0
~
Fmax
Hz
0.00
●
F9-05=0
Defined by the value of F9-06.
F9-05=1
Set by VP keypad potentiometer.
F9-05=2
Set by the voltage of analog terminal VS.
F9-05=3
Set by the current of analog terminal IS.
F9-05=5
Set by K3*VS+K4*IS (Input signals VS and IS)
F9-05=6
Setting frequency is set by K3*VS+K5*VF (Input voltage signals VS and VF)
F9-05=7
Setting frequency is set by: K4*IS+K6*IF (Input current signals IS and IF)
F9-05=8
Setting frequency is set by the greater value between K3*VS and K5*VF (Inputs
of 2 terminals)
F9-05=9
Setting frequency is set by the greater value between K4*IS and K6*IF (Inputs of
2 terminals)
F9-05=10
Setting frequency is set by:
K1*VP+K2*(K3*VS+K4*IS+K5*VF+K6*IF-K8*5V) (All input signals)
8.11.6
Multi-function Output Related to Frequency Detection
No.
Function
Range
Unit Default Type
F9-09
Frequency of Zero Speed
Detection
0.00
~
50.00/0.0
~
50.0 Hz
0.00
〇
If multi-function output or relay output=20 (Frequency of zero speed detection), and when
inverter is running, if the output frequency < the setting value of F9-09, it will be considered
as inverter runs at zero speed, and the corresponding output terminal will be on.
No.
Function
Range
Unit Default Type
F9-10
Zero Speed Detection Output Delay 0.00
~
600.00
S
1.00
〇
F9-10 is to delay the action of output terminal corresponding to zero speed detection when
zero speed detection is enabled.