deceleration, t1 = the setting value of FC-01* Deceleration time, t2= the setting value of
FC-02* Deceleration time.
Acceleration Time
t1
t2
t2
t1
S Curve
Mode
Linear
Mode
Frequency
t
t
Deceleration Time
Figure 7-23 Acceleration/Deceleration Control
8.13.2
Fan Control
No.
Function
Range
Unit Default Type
FC-03
Fan Control
0: Run at power-on
1: Run at start-up
1
〇
FC-04
Fan Delay Time
0.00~600.00
S
30.00
●
FC-03
selects the conditions for fan to run.
FC-03=0
Fan runs at power-on.
FC-03=1
Fan runs while inverter is running.
FC-04
selects the delay time for fan turned-on. In default status, the fan will stop after the
inverter is stopped for 30 seconds.
8.13.3
Reset Previous Working Status
No.
Function
Range
Unit Default Type
FC-06
Reset previous working
status at power-on
0: Not Reset
1: Reset
0
〇
FC-06=0
Inverter will not reset previous working status.
FC-06=1
Inverter remains the previous work status before power failure after it was
powered-on.
8.13.4
Current Control and Energy Saving
No.
Function
Range
Unit Default Type
FC-07
Current Stall Control
0: Disabled
1: Not Used
2: Enabled
2
〇
FC-08
Overcurrent Stall Current
50.00
~
180.00
%
150.00
〇
FC-09
Current Limit Coefficient of Weak
Flux
0.20
~
1.00
0.70
〇