User Manual
EM303B General Purpose Inverter
55
6.2.2
F1 Group: Motor Parameters
No.
Function
Range
Unit Default Type S/N
F1-00
Motor Type
0: AC induction motor
1: Not used
0
〇
32
F1-01
Motor Rated Power
0.40~480.00
kW
XXXX
〇
33
F1-02
Motor Rated Voltage
60~660
V
XXX
〇
34
F1-03
Motor Rated Current
0.1~1500.0
A
XXXX
〇
35
F1-04
Motor Rated Frequency
20.00~600.00
Hz
XXXX
〇
36
F1-05
Motor Rated Speed
1~60000
rpm
XXXX
〇
37
F1-06
Motor Wiring Mode
0
:
Y
1
:
Δ
X
〇
38
F1-07
Motor Rated Power Factor 0.50~0.99
X
〇
39
F1-08
Idling Excitation Current I0 0.1~1500.0
A
XXXX
〇
40
F1-09
Rated Torque Current
0.1~1500.0
A
XXXX
×
41
F1-10
Stator Resistance R1
0.001~60.000
Ω
XXXX
〇
42
F1-11
Rotator Resistance R2
0.001~60.000
Ω
XXXX
〇
43
F1-12
Stator& Rotor Leakage
Inductance Ls
0.1~3000.0
mH
XXXX
〇
44
F1-13
Stator& Rotor Mutual
Inductance Lm
0.1~3000.0
mH
XXXX
〇
45
F1-14
Motor Efficiency
30.0~99.0
XXX
〇
46
F1-15
Autotuning Parameters
0: No autotuning
1: Stationary autotuning
2: Rotational autotuning
0
〇
47
F1-16
Inverter Address
1
~
247,
0: Broadcasting Address
1
〇
48
F1-17
Communication Bit Rate
0: 4800
1: 9600
2: 19200
3: 38400
bps
1
〇
49
F1-18
Communication Parity
Mode
0: No parity 1+8+1 for RTU
1: Even parity 1+8+1+1 for RTU
2: Odd parity 1+8+1+1 for RTU
0
〇
50
F1-19
Master-slave
Communication Mode
0: The inverter is the slave
1: The inverter is the master
0
〇
51
F1-20
Receiving Address of Slave
Inverter
0:Primary Numeric Frequency (F0-07)
1:Auxiliary Numeric Frequency( F9-06)
0
〇
52
F1-21
Inverter Receiving
Proportion Coefficient
0.00~600.00
%
100.00
●
53
F1-22
Analog Input Gain K1
0.00~600.00
%
100.00
●
54
F1-23
Analog Input Gain K2
0.00~600.00
%
0.00
●
55
F1-24
Analog Input Gain K3
0.00~600.00
%
100.00
●