User Manual
EM303B General Purpose Inverter
45
Flashing
Flashing
Flashing
Quickly
Flashing
闪烁
RES
ESC
RES
ESC
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
RES
ESC
RES
ESC
RES
ESC
RES
ESC
RES
ESC
RES
ESC
Flashing
Flashing
Quickly
Flashing
Figure 4-6 Procedures of Saving and Resetting Parameter
Saving Parameters of Relevant Function Code
Because there are correlations between some parameters, the relevant parameters will be
edited and saved when corresponding function code has been edited and saved.
The function codes which have correlations:
1.
Maximum frequency (F0-16)
The frequencies related to inverter’s operation < F0-16(Maximum frequency). When editing
and saving the maximum frequency, if the other relevant frequencies > the maximum
frequency, inverter will limit the relevant frequency as the maximum frequency. If they are
less than the maximum frequency, the relevant frequencies remain unchanged.
The function codes are correlative with each other: F0-07 Primary numeric setting frequency
setting, F0-17 upper limit frequency, F0-18 lower limit frequency, and F3-00~F3-14 Preset
speed setting.
2.
Customer defined V/F curve setting
The function code of customer defined V/F curve setting: Fd-05~Fd-08, the correlation of
them: 0≤Fd-05≤Fd-06≤Fd-07≤Fd-08≤F1-04.
3.
Upper/Lower limit frequency (F0-17, F0-18)
F0-17(Upper Limit Frequency)≥F0-18(Lower Limit Frequency)
4.
Skip frequencies (F6-16, F6-18, F6-20)
F6-16≤F6-18≤F6-20