User Manual
EM303B General Purpose Inverter
101
No.
Function
Description
4
Output Frequency
Detection Range FDT1
(Disabled at JOG)
When inverter is running (Except in JOG running mode), if
the output frequency increases to the value of F9-12 (FDT1
Increasing Threshold), the output terminal is on. If the
output frequency drops and is less than the value of F9-13
(FDT1 Decreasing Threshold), the output terminal is off.
See 7.13.3 for details.
5
Output Frequency
Detection Range FDT2
(Disabled at JOG)
When inverter is running (Except in JOG mode), if the
output frequency increases to the value of F9-14 (FDT2
Increasing Threshold), the output terminal is on. If the
output frequency drops and is less than the value of F9-15
(FDT2 Decreasing Threshold), the output terminal is off.
See 7.13.3 for details.
6
Forward/Reverse
(Enabled at Running)
When inverter is running, if the motor reverses, the output
terminal is on. If the motor forwards, the output terminal is
off.
7
Frequency Input/Output
Balance
(Enabled at Running)
When inverter is running, if output frequency= the setting
frequency, the output terminal is on.
8
JOG
When inverter is jogging, the output terminal is on.
9
Inverter Fault
When inverter trips fault, the output terminal is on.
10
Upper Limit Frequency
Reach(Enabled at
Running)
When the output frequency of inverter reaches the setting
upper limit frequency of F0-17, the output terminal is on.
11
Lower Limit Frequency
Reach(Enabled at
Running)
When the output frequency reached the lower limit
frequency set by F0-18, the output terminal is on. (The
output terminal will be off when accelerating to the lower
limit frequency at the initial running. When the output
frequency exceeds the lower limit frequency at the first time,
and then reaches lower limit frequency again, the output
terminal is on.)
12
Not Used
13
Not Used
14
Analog Variables
Detection Range ADT1
If the input signal of analog input terminal> the value of
ADT1 set by F7-05, the output terminal is on. See 7.9.2 for
details.
15
Analog Variables
Detection Range ADT2
If the input signal of analog input terminal> the value of
ADT2 set by F7-07, the output terminal is on. See 7.9.2 for
details.
16
Analog Variables
Detection Range ADT3
If the input signal of analog input terminal> the value of
ADT1 set by F7-09, the output terminal is on. See 7.9.2 for
details.
17
Overload Alarming
Output
When the present current of inverter exceeds the overload
detection scale and the remaining time exceeds the overload
detection time. See 7.9.1 for details.