immediately. See Table 7-5 for the programming mode of acceleration/deceleration time
terminal 1 and 2.
Table 7-5 Programming Mode of Acceleration/Deceleration Time Terminals
Acceleration/Deceleration
Time Terminal 1
Acceleration/Deceleration
Time Terminal 2
Acceleration
Time/No.
Deceleration
Time/No.
OFF
OFF
1 F0-09
1 F0-10
ON
OFF
2 F3-15
2 F3-16
OFF
ON
3 F3-17
3 F3-18
ON
ON
4 F3-19
4 F3-20
As shown in Table 7-5, acceleration/decelerationtime refers to acceleration time 1 and
deceleration time 1 in regular operation mode without using acceleration/deceleration
terminal.
No.
Function
Range
Unit Default Type
F3-21
Acceleration/Deceleration
Time Unit
0: S
1: min
0
〇
F3-21=0
The unit of acceleration/deceleration time is second. The acceleration/deceleration
time can be set continuously in the range of 0.00
~
600.00 seconds.
F3-21=1
The unit of acceleration/deceleration time is minute. The acceleration/deceleration
time can be set continuously in the range of 0.00
~
600.00 minutes.
No.
Function
Range
Unit Default Type
F3-22
DC Brake Proportion at Start
0.00
~
30.00,
30.01
~
250.00
%
100.00
〇
F3-23
DC Brake Time at Start
0.00
~
30.00
S
0.00
〇
Before inverter starts, the motor may run in low speed or reverse. If inverter starts
immediately at the moment, overcurrent may occur. In order to avoid such faults, please start
DC brake to stop motor before inverter starts, and then the inverter runs to setting frequency
as per setting direction.
F3-22
Different setting values can define different DC brake torques at start.
If F3-22≤30.00, the percentage base is the rated output voltage of inverter. While, the DC
brake controls the DC voltage generated by motor windings.
If F3-22≥30.01, the percentage base is the rated output current of inverter. While, the DC
brake controls the DC current generated by motor windings.
If F3-22≤30.00, inverter will trip overcurrent fault in the process of DC brake. Please
reduce the value of F3-22 or set F3-22
>
30.00.
F3-23
Set the DC brake time at start. Inverter runs immediately when the time is up. If
F3-23=0.00, DC brake is disabled at start.
★
The DC brake process at start is as shown in Figure 7-10.
The function is applicable to that one inverter drives multi-motors.