User Manual
EM303B General Purpose Inverter
91
1. When reverse is permitted, inverter will judge present running direction based
on the setting of F0-08 and the status of terminal F/R. If F0-08=1 and terminal F/R
is on, inverter runs forward.
2. If the setting forward direction of inverter is not identical with the expected running
direction of motor, switch any two of output cables (U, V, and W) of inverter or set
F0-08=1.
No.
Function
Range
Unit Default Type
F0-26
Primary Speed Setting
Mode
0: Regular speed setting mode
1: Special speed setting mode
2: Process PID input mode
0
〇
F0-26=0
Primary speed setting mode is the regular speed setting mode. Primary numeric
speed setting mode or analog signal setting mode can be set by selecting parameter of F0-06.
F0-26=1
Primary speed setting mode is the special speed setting mode. Special speed setting
mode can be selected as program running or stepping speed setting mode by advanced
running mode.
F0-26=2
Primary speed setting mode is process PID input mode. Numeric PID setting mode
or analog signal setting mode can be selected via F4-00.
No.
Function
Range
Unit Default Type
F0-27
Menu Mode Options
0: Basic menu mode
1: Advanced menu mode
0
〇
F0-27=0
Keypad only displays the basic setting parameters of F0~F5. (6-group parameters
could meet the needs of most of applications.)
F0-27=1
Keypad displays 17-group parameters of F0~FF for users to set parameters.
No.
Function
Range
Unit Default Type
F0-28
Default Control
0: Disabled
1: Defaults Reset
0
〇
No.
Function
Range
Unit Default Type
F0-29
Parameter Setting Control
0: Parameter setting permitted
1: Parameter lock 0
2: Parameter lock 1
0
〇
Reset Default
F0-28=1 Reset Default:
Except motor parameters in Group F1 Group and FA Group, and
inverter parameters in Fd Group, the rest of parameters will reset to default. After reset
completed, F0-28=0.
Parameter Lock
F0-29=0
All parameters are allowed to be edited.
F0-29=1Parameter lock 0
Lock parameters except numeric settings. The numeric settings are primary numeric
frequency setting F0-07, auxiliary numeric frequency setting F9-06, jog running frequency