User Manual
EM303B General Purpose Inverter
157
If settingFd-11
≠
0, the system will enter VF separation mode.After entering VF separation
mode, please set F0-28=1, the parameters will be of VF separation mode.
Remarks:
When setting Fd-11=0 and F0-28=1, and pressing enter, the parameters will be
reset to defaults. The system will exit VF separation mode.
No.
Function
Range
Unit
Default
Type
Fd-12
Voltage Change Time
0.00
~
60.00
S
5.00
●
Fd-12
is for adjusting the change rate of VF separation mode. The change base is
changing time of 0%~100%.
。
No.
Function
Range
Unit
Default
Type
FC-15
Output Voltage
0.00
~
100.00
%
100.00
●
When Fd-11=1, FC-15 is for adjusting output voltage. 0~380V is corresponding to
0%~100%.
8.14.4
Review Inverter Parameters
No.
Function
Range
Unit Default Type
Fd-21
Inverter Rated Power
0.40~480.00
kW XXXX
X
Fd-22
Inverter Rated Voltage
60~660
V
XXX
X
Fd-23
Inverter Rated Current
0.1~1500.0
A
XXXX
X
Parameters of Fd-21~ Fd-23are read only for the users. Please check if the parameters are in
accordance with the nameplate before inverter start-up.
8.14.5
Review and Setting Running Time of Inverter
No.
Function
Range
Unit
Default Type
Fd-24
Inverter Running Time
User monitoring
HOUR XXXX
X
Fd-25
Inverter Running Time
User monitoring
min
XXXX
X
Fd-26
Running Time Control
0:Disabled
1:Enabled
0
-
Fd-27
Set Running Time
0
~
65535
HOUR 0
-
Parameters of Fd-24~ Fd-27 are read only for the users. When running timeance with the
nameplate before invert would not work. If inverter runs again, it will trip fault INP (Internal
Trip).
No.
Function
Range
Unit Default Type
Fd-28
Distributor Password
Fd-29
Manufacturer Password
Fd-28~ Fd-29are for professionals only. It is to prevent the fault caused by editing the key
parameters of inverter.
8.14.6
Reviewing Software Version
No.
Function
Range
Unit Default Type
Fd-20
CPUB Software Version
X.XX
X.XX
X
Fd-30
Keypad Software Version
X.XX
X.XX